Function test and condition test for disconnecting circuit breakers
KTH, School of Electrical Engineering (EES), Electromagnetic Engineering. (RCAM)ORCID iD: 0000-0002-2462-8340
KTH, School of Electrical Engineering (EES), Electromagnetic Engineering. (RCAM)ORCID iD: 0000-0002-2964-7233
2015 (English)Conference paper, Published paper (Refereed)
Abstract [en]

Svenska kraftnät has installed about 300 disconnecting circuit breakers (DCB) in the Swedish 245 and 420 kV transmission network. They are installed without any disconnectors in the substation. The first DCBs were installed in the early 2000s and are approaching the age of 12 years, which is the time for the first scheduled maintenance, a function test that requires de-energising of the breaker. For a shunt reactor breaker in a double-breaker double-busbar configuration this means disconnection of one of the busbars at the substation, whereas for a line breaker it means disconnection of the incoming line, which is often difficult.

 

Thus for disconnecting circuit breakers especially line breakers, there is need for an in-service condition test, which have been developed and tested at Svenska kraftnät. It requires some modification to the DCBs from the manufacturer and has been a Svenska kraftnät standard for many years.

 

This paper describes the difference between the conventional off-line function test and the new in-service condition test, mainly regarding the possible failures that can be detected. The failures can be classified in three major types: mechanical, electrical and related to the insulation gas. The present condition test measures the movements during the opening and closing operations and it can assess the condition of the mechanical parts, whereas the condition of breaking chamber and the electrical resistance of the contacts are not possible to measure without disconnecting the circuit breaker. The gas pressure and other parameters can be added separately to the condition test. Also this paper provides normal values of the parameters measured in an in-service condition test, such as coil current, motor current and timing parameters.

Place, publisher, year, edition, pages
Nagoya, Japan: CIGRE SC A3 & B3 and the Japanese National Committee of CIGRE , 2015. Vol. 305
Keywords [sv]
frånskiljande brytare, funtionskontroll, tillståndskontroll, öppning, slutning, disconnecting circuit breaker, function test, condition test, opening operation, closing operation
National Category
Other Electrical Engineering, Electronic Engineering, Information Engineering
Research subject
Electrical Engineering
Identifiers
URN: urn:nbn:se:kth:diva-177137OAI: oai:DiVA.org:kth-177137DiVA, id: diva2:871546
Conference
2015 CIGRE SC A3 & B3 joint colloquium
Funder
SweGRIDS - Swedish Centre for Smart Grids and Energy Storage, CIPOWER
Note

QC 2016-02-11

Available from: 2015-11-16 Created: 2015-11-16 Last updated: 2024-03-18Bibliographically approved

Open Access in DiVA

No full text in DiVA

Authority records

Westerlund, PerHilber, Patrik

Search in DiVA

By author/editor
Westerlund, PerHilber, Patrik
By organisation
Electromagnetic Engineering
Other Electrical Engineering, Electronic Engineering, Information Engineering

Search outside of DiVA

GoogleGoogle Scholar

urn-nbn

Altmetric score

urn-nbn
Total: 416 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf