Frost prediction in heat exchangers: The influence of relative humidity and outdoor temperature on frost formation in plate heat exchangers
KTH, Skolan för arkitektur och samhällsbyggnad (ABE), Byggvetenskap, Betongbyggnad.
2022 (Engelska)Självständigt arbete på avancerad nivå (masterexamen), 20 poäng / 30 hpStudentuppsats (Examensarbete)
Abstract [en]

Frost in Mechanical Ventilation with Heat Recovery (MVHR) often occurs when indoor air is humid and outdoor air is cold. Warm and humid air from the rooms condensates or sublimates when it becomes cold enough, causing frost to grow in the heat exchanger channels. These layers of frost introduce a pressure loss over the heat exchanger and act as an insulating layer, lowering the heat recovery rate of the heat exchanger. It can also buckle the heat exchanger plates and cause long-term damage. The report outlines a method to calculate the frost limit curve for residential parallel and counter flow heat exchangers. A real heat exchanger model from company Swegon is used to provide an example of the method being used. The method involves a well-known Number of Transfer Units (NTU) equation for calculating the dry conditions temperature profile, and an approximation is used for calculation of the temperature profile under wet conditions. The lowest allowable outdoor temperature increases rapidly for increasing relative humidity up to approximately 30%, at which point it tapers off slowly. The results also show that condensation in the heat exchanger increases the lowest allowed temperature in comparison to an identical heat exchanger with no condensation. Lastly, the results show that the distance between plates change the frost limit curve considerably, with a smaller distance between plates being worse for frost risks.

Ort, förlag, år, upplaga, sidor
2022.
Serie
TRITA-ABE-MBT ; 22640
Nationell ämneskategori
Teknik och teknologier
Identifikatorer
URN: urn:nbn:se:kth:diva-317450OAI: oai:DiVA.org:kth-317450DiVA, id: diva2:1694867
Externt samarbete
Bravida; Uponor
Handledare
Examinatorer
Tillgänglig från: 2022-09-12 Skapad: 2022-09-12

Open Access i DiVA

fulltext(1979 kB)1544 nedladdningar
Filinformation
Filnamn FULLTEXT01.pdfFilstorlek 1979 kBChecksumma SHA-512
cdb486ff44a71d9e4fba865cb8068ef5b02e4e62346b048f8de0f340cfa97207febabf7ba85ae6afd0d27273b4f2dfe5201e5ddc7c1ab543d1ede371bd329245
Typ fulltextMimetyp application/pdf

Av organisationen
Betongbyggnad
Teknik och teknologier

Sök vidare utanför DiVA

GoogleGoogle Scholar
Totalt: 1571 nedladdningar
Antalet nedladdningar är summan av nedladdningar för alla fulltexter. Det kan inkludera t.ex tidigare versioner som nu inte längre är tillgängliga.

urn-nbn

Altmetricpoäng

urn-nbn
Totalt: 1364 träffar
RefereraExporteraLänk till posten
Permanent länk

Direktlänk
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annat format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annat språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf