Energy efficient and economic renovation of residential buildings with low-temperature heating and air heat recovery
KTH, Skolan för arkitektur och samhällsbyggnad (ABE), Byggvetenskap, Strömnings- och klimatteknik.
2015 (Engelska)Licentiatavhandling, sammanläggning (Övrigt vetenskapligt)
Abstract [en]

With the building sector accounting for around 40% of the total energy consumption in the EU, energy efficiency in buildings is and continues to be an important issue. Great progress has been made in reducing the energy consumption in new buildings, but the large stock of existing buildings with poor energy performance is probably an even more crucial area of focus. This thesis deals with energy efficiency measures that can be suitable for renovation of existing houses, particularly low-temperature heating systems and ventilation systems with heat recovery. The energy performance, environmental impact and costs are evaluated for a range of system combinations, for small and large houses with various heating demands and for different climates in Europe. The results were derived through simulation with energy calculation tools.

Low-temperature heating and air heat recovery were both found to be promising with regard to increasing energy efficiency in European houses. These solutions proved particularly effective in Northern Europe as low-temperature heating and air heat recovery have a greater impact in cold climates and on houses with high heating demands. The performance of heat pumps, both with outdoor air and exhaust air, was seen to improve with low-temperature heating. The choice between an exhaust air heat pump and a ventilation system with heat recovery is likely to depend on case specific conditions, but both choices are more cost-effective and have a lower environmental impact than systems without heat recovery. The advantage of the heat pump is that it can be used all year round, given that it produces DHW.

Economic and environmental aspects of energy efficiency measures do not always harmonize. On the one hand, lower costs can sometimes mean larger environmental impact; on the other hand there can be divergence between different environmental aspects. This makes it difficult to define financial subsidies to promote energy efficiency measures.

Abstract [sv]

Byggnader står för omkring 40 % av den totala energianvändningen i EU. Energieffektivisering av byggnader är och fortsätter därför att vara en viktig fråga. Även om stora framsteg har gjorts när det gäller att minska energianvändningen i nya byggnader så är det stora beståndet av befintliga byggnader med dålig energiprestanda förmodligen ett ännu viktigare område att fokusera på. Denna avhandling behandlar energieffektiviseringsåtgärder som kan lämpa sig för renovering av befintliga hus, i synnerhet lågtemperaturvärmesystem och ventilationssystem med värmeåtervinning. Energiprestanda, miljöpåverkan och kostnader utvärderas för en rad systemkombinationer, för små och stora hus med olika värmebehov och för olika klimat i Europa. Resultaten togs fram genom simuleringar med energiberäkningsprogram.

Lågtemperatursystem och värmeåtervinning framstod båda som lovande lösningar för energieffektivisering av europeiska hus, särskilt i norra Europa, eftersom dessa åtgärder har större effekt i kalla klimat och på hus med stort värmebehov. Prestandan för värmepumpar, såväl av utelufts- som frånluftstyp, förbättrades med lågtemperaturvärmesystem. Valet mellan frånluftsvärmepump och värmeåtervinning till ventilationsluft kan antas bero på specifika förhållanden för varje fall, men de är båda mer kostnadseffektiva och har lägre miljöpåverkan än system utan värmeåtervinning. Värmepumpen har fördelen att den kan återvinna värme året runt, förutsatt att den producerar varmvatten.

Ekonomiska och miljömässiga aspekter av energieffektiviseringsåtgärder stämmer inte alltid överens. Dels lägre kostnad ibland betyda större miljöpåverkan, dels kan det finnas divergens mellan olika miljöaspekter. Detta gör det svårt att fastställa subventioner för att främja energieffektiviseringsåtgärder.

Ort, förlag, år, upplaga, sidor
Stockholm: KTH Royal Institute of Technology, 2015. , s. vii, 27
Serie
TRITA-STKL
Nationell ämneskategori
Miljöanalys och bygginformationsteknik
Forskningsämne
Energiteknik
Identifikatorer
URN: urn:nbn:se:kth:diva-172982ISBN: 978-91-7595-664-0 (tryckt)OAI: oai:DiVA.org:kth-172982DiVA, id: diva2:851312
Presentation
2015-09-18, Övningssal 25, Brinellvägen 23, KTH, Stockholm, 13:00 (Engelska)
Opponent
Handledare
Anmärkning

QC 20150904

Tillgänglig från: 2015-09-04 Skapad: 2015-09-04 Senast uppdaterad: 2015-09-04Bibliografiskt granskad
Delarbeten
1. Energy performance comparison of three innovative HVAC systems for renovation through dynamic simulation
Öppna denna publikation i ny flik eller fönster >>Energy performance comparison of three innovative HVAC systems for renovation through dynamic simulation
Visa övriga...
2014 (Engelska)Ingår i: Energy and Buildings, ISSN 0378-7788, E-ISSN 1872-6178, Vol. 82, s. 512-519Artikel i tidskrift (Refereegranskat) Published
Abstract [en]

In this paper, dynamic simulation was used to compare the energy performance of three innovativeHVAC systems: (A) mechanical ventilation with heat recovery (MVHR) and micro heat pump, (B) exhaustventilation with exhaust air-to-water heat pump and ventilation radiators, and (C) exhaust ventilationwith air-to-water heat pump and ventilation radiators, to a reference system: (D) exhaust ventilation withair-to-water heat pump and panel radiators. System A was modelled in MATLAB Simulink and systems Band C in TRNSYS 17. The reference system was modelled in both tools, for comparison between the two.All systems were tested with a model of a renovated single family house for varying U-values, climates,infiltration and ventilation rates.It was found that A was the best system for lower heating demand, while for higher heating demandsystem B would be preferable. System C was better than the reference system, but not as good as A or B.The difference in energy consumption of the reference system was less than 2 kWh/(m2a) betweenSimulink and TRNSYS. This could be explained by the different ways of handling solar gains, but also bythe fact that the TRNSYS systems supplied slightly more than the ideal heating demand.

Ort, förlag, år, upplaga, sidor
Elsevier, 2014
Nyckelord
Energy performance, Dynamic simulation, HVAC, Micro heat pump, Heat recovery, Ventilation radiator, TRNSYS, MATLAB Simulink, Renovation
Nationell ämneskategori
Energiteknik
Forskningsämne
Energiteknik; Byggvetenskap
Identifikatorer
urn:nbn:se:kth:diva-150447 (URN)10.1016/j.enbuild.2014.07.059 (DOI)000343781400050 ()2-s2.0-84906314530 (Scopus ID)
Projekt
iNSPiRe
Forskningsfinansiär
EU, FP7, Sjunde ramprogrammet, 314461
Anmärkning

QC20140912

Tillgänglig från: 2014-09-04 Skapad: 2014-09-04 Senast uppdaterad: 2017-12-05Bibliografiskt granskad
2. Techno-economic analysis of energy renovation measures for a district heated multi-family house
Öppna denna publikation i ny flik eller fönster >>Techno-economic analysis of energy renovation measures for a district heated multi-family house
Visa övriga...
2016 (Engelska)Ingår i: Applied Energy, ISSN 0306-2619, E-ISSN 1872-9118, Vol. 177, s. 108-116Artikel i tidskrift (Refereegranskat) Published
Abstract [en]

Renovation of existing buildings is important in the work towards increased energy efficiency and reduced environmental impact. The present paper treats energy renovation measures for a Swedish district heated multi-family house, evaluated through dynamic simulation. Insulation of roof and façade, better insulating windows and flow-reducing water taps, in combination with different HVAC systems for recovery of heat from exhaust air, were assessed in terms of life cycle cost, discounted payback period, primary energy consumption, CO₂ emissions and non-renewable energy consumption. The HVAC systems were based on the existing district heating substation and included mechanical ventilation with heat recovery and different configurations of exhaust air heat pump.

Compared to a renovation without energy saving measures, the combination of new windows, insulation, flow-reducing taps and an exhaust air a heat pump gave up to 24% lower life cycle cost. Adding insulation on roof and façade, the primary energy consumption was reduced by up to 58%, CO₂ emissions up to 65% and non-renewable energy consumption up to 56%. Ventilation with heat recovery also reduced the environmental impact but was not economically profitable in the studied cases. With a margin perspective on electricity consumption, the environmental impact of installing heat pumps or air heat recovery in district heated houses is increased. Low-temperature heating improved the seasonal performance factor of the heat pump by up to 11% and reduced the environmental impact.

Ort, förlag, år, upplaga, sidor
Elsevier, 2016
Nyckelord
District heating, air heat recovery, heat pump, LCC, primary energy, low-temperature heating
Nationell ämneskategori
Miljöanalys och bygginformationsteknik Energisystem
Forskningsämne
Energiteknik
Identifikatorer
urn:nbn:se:kth:diva-172979 (URN)10.1016/j.apenergy.2016.05.104 (DOI)000380623900010 ()2-s2.0-84969776538 (Scopus ID)
Anmärkning

QC 20160809

Tillgänglig från: 2015-09-04 Skapad: 2015-09-04 Senast uppdaterad: 2017-12-04Bibliografiskt granskad
3. Comparison of two HVAC renovation solutions: A case study
Öppna denna publikation i ny flik eller fönster >>Comparison of two HVAC renovation solutions: A case study
2013 (Engelska)Ingår i: CLIMA 2013, Prague, June 16-19, 2013, 2013Konferensbidrag, Muntlig presentation med publicerat abstract (Refereegranskat)
Abstract [en]

Within the aging building stock of Europe, there is great potential of saving energy through renovation and upgrading to modern standards, and to thereby approach the internationally set goals of lower energy use. This paper concerns the planned renovation of the building envelope and HVAC systems in a multi-family house in Ludwigsburg, Germany. Five systemic HVAC solutions were compared, with special focus on two systems: A) Balanced ventilation with HRC + Micro heat pump, and B) Forced exhaust ventilation + Heat pump with exhaust air HRC + Ventilation radiators. Given the predicted heating demand and ventilation rate of the house after renovation, the performance of the two systems was compared, alongside three common systems for reference. Calculations were made using TMF Energi, a tool developed by SP Technical Research Institute of Sweden.

Both systems A and B were found to have the lowest electrical energy use together with the ground source heat pump system for the assumed conditions. For other assumptions, including different climate and degree of insulation, some differences between these three systems were noted. Most significant is the increased electrical use of system B for higher heating loads due to limitations in the power available from the heat source, exhaust air, which is dependent on the ventilation rate.

Nyckelord
energy renovation; HVAC; system comparison; low-energy house; ventilation radiator; micro heat pump
Nationell ämneskategori
Energiteknik
Identifikatorer
urn:nbn:se:kth:diva-136293 (URN)
Konferens
CLIMA 2013, Prague, June 16-19, 2013
Forskningsfinansiär
EU, FP7, Sjunde ramprogrammet, 314461
Anmärkning

QC 20131218

Tillgänglig från: 2013-12-04 Skapad: 2013-12-04 Senast uppdaterad: 2015-09-04Bibliografiskt granskad
4. Techno-economic analysis of three HVAC retrofitting options
Öppna denna publikation i ny flik eller fönster >>Techno-economic analysis of three HVAC retrofitting options
2014 (Engelska)Konferensbidrag, Muntlig presentation med publicerat abstract (Refereegranskat)
Abstract [en]

Accounting for around 40% of the total final energy consumption, the building stock is an important area of focus on the way to reaching the energy goals set for the European Union. The relatively small share of new buildings makes renovation of existing buildings possibly the most feasible way of improving the overall energy performance of the building stock. This of course involves improvements on the climate shell, for example by additional insulation or change of window glazing, but also installation of new heating systems, to increase the energy efficiency and to fit the new heat load after renovation. In the choice of systems for heating, ventilation and air conditioning (HVAC), it is important to consider their performance for space heating as well as for domestic hot water (DHW), especially for a renovated house where the DHW share of the total heating consumption is larger.

The present study treats the retrofitting of a generic single family house, which was defined as a reference building in a European energy renovation project. Three HVAC retrofitting options were compared from a techno-economic point of view: A) Air-to-water heat pump (AWHP) and mechanical ventilation with heat recovery (MVHR), B) Exhaust air heat pump (EAHP) with low-temperature ventilation radiators, and C) Gas boiler and ventilation with MVHR. The systems were simulated for houses with two levels of heating demand and four different locations: Stockholm, Gdansk, Stuttgart and London. They were then evaluated by means of life cycle cost (LCC) and primary energy consumption. Dynamic simulations were done in TRNSYS 17.

In most cases, system C with gas boiler and MVHR was found to be the cheapest retrofitting option from a life cycle perspective. The advantage over the heat pump systems was particularly clear for a house in Germany, due to the large discrepancy between national prices of natural gas and electricity. In Sweden, where the price difference is much smaller, the heat pump systems had almost as low or even lower life cycle costs than the gas boiler system. Considering the limited availability of natural gas in Sweden, systems A and B would be the better options. From a primary energy point of view system A was the best option throughout, while system B often had the highest primary energy consumption. The limited capacity of the EAHP forced it to use more auxiliary heating than the other systems did, which lowered its COP. The AWHP managed the DHW load better due to a higher capacity, but had a lower COP than the EAHP in space heating mode. Systems A and C were notably favoured by the air heat recovery, which significantly reduced the heating demand.

It was also seen that the DHW share of the total heating consumption was, as expected, larger for the house with the lower space heating demand. This confirms the supposition that it is important to include DHW in the study of HVAC systems for retrofitting.

Nyckelord
HVAC, retrofit, techno-economic, heat pump, ventilation radiator, gas boiler, LCC, primary energy, dynamic simulation
Nationell ämneskategori
Energiteknik
Forskningsämne
Energiteknik; Byggvetenskap
Identifikatorer
urn:nbn:se:kth:diva-150454 (URN)
Konferens
Roomvent 2014
Projekt
iNSPiRe
Forskningsfinansiär
EU, FP7, Sjunde ramprogrammet, 314461
Anmärkning

QC 20150305

Tillgänglig från: 2014-09-04 Skapad: 2014-09-04 Senast uppdaterad: 2015-09-04Bibliografiskt granskad

Open Access i DiVA

Thesis(1227 kB)415 nedladdningar
Filinformation
Filnamn FULLTEXT01.pdfFilstorlek 1227 kBChecksumma SHA-512
a037d9ca81ed5f3003cda6400e0ce502bc13c97220e125200b6796182f723bd67cdaf1e21b67c359095c975a95caeabd95d9c031e6175d4763639519b2994ad8
Typ fulltextMimetyp application/pdf

Sök vidare i DiVA

Av författaren/redaktören
Gustafsson, Marcus
Av organisationen
Strömnings- och klimatteknik
Miljöanalys och bygginformationsteknik

Sök vidare utanför DiVA

GoogleGoogle Scholar
Totalt: 415 nedladdningar
Antalet nedladdningar är summan av nedladdningar för alla fulltexter. Det kan inkludera t.ex tidigare versioner som nu inte längre är tillgängliga.

isbn
urn-nbn

Altmetricpoäng

isbn
urn-nbn
Totalt: 920 träffar
RefereraExporteraLänk till posten
Permanent länk

Direktlänk
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annat format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annat språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf