Distributed Thermal Response Tests on a Multi-pipe Coaxial Borehole Heat Exchanger
KTH, School of Industrial Engineering and Management (ITM), Energy Technology, Applied Thermodynamics and Refrigeration.ORCID iD: 0000-0002-3490-1777
KTH, School of Industrial Engineering and Management (ITM), Energy Technology, Applied Thermodynamics and Refrigeration.ORCID iD: 0000-0002-9902-2087
2011 (English)In: HVAC & R RESEARCH, ISSN 1078-9669, E-ISSN 1938-5587, Vol. 17, no 6, p. 1012-1029Article in journal (Refereed) Published
Abstract [en]

In a distributed thermal response test, distributed temperature measurements are taken along a borehole heat exchanger during thermal response tests, allowing the determination of local ground thermal conductivities and borehole thermal resistances. In this article, the first results from six heat injection distributed thermal response tests carried out on a new, thermally insulated leg type, multi-pipe coaxial borehole heat exchanger are presented. The borehole heat exchanger consists of 1 insulated central and 12 peripheral pipes. Temperature measurements are carried out using fiber-optic cables placed inside the borehole heat exchanger pipes. Unique temperature and thermal power profiles along the borehole depth as a function of the flow rate and the total thermal power injected into the borehole are presented. A line source model is used for simulating the borehole heat exchanger thermal response and determining local variations of the ground thermal conductivity and borehole thermal resistance. The flow regime in the peripheral pipes is laminar during all distributed thermal response tests and average thermal resistances remain relatively constant, independently of the volumetric flow rate, being lower than those corresponding to U-pipe borehole heat exchangers. The thermal insulation of the central pipe significantly reduces the thermal shunt to the peripheral pipes even at low volumetric flow rates.

Place, publisher, year, edition, pages
London: Taylor & Francis, 2011. Vol. 17, no 6, p. 1012-1029
Keywords [en]
Ground Source Heat Pump, Borehole Heat Exchanger
National Category
Energy Engineering
Identifiers
URN: urn:nbn:se:kth:diva-73091DOI: 10.1080/10789669.2011.625304ISI: 000299958700010Scopus ID: 2-s2.0-84861615998OAI: oai:DiVA.org:kth-73091DiVA, id: diva2:488536
Projects
EFFSYS2EFFSYS+
Note

QC 20120222

Available from: 2012-02-01 Created: 2012-02-01 Last updated: 2022-06-24Bibliographically approved
In thesis
1. Distributed thermal response tests: New insights on U-pipe and Coaxial heat exchangers in groundwater-filled boreholes
Open this publication in new window or tab >>Distributed thermal response tests: New insights on U-pipe and Coaxial heat exchangers in groundwater-filled boreholes
2013 (English)Doctoral thesis, comprehensive summary (Other academic) [Artistic work]
Abstract [en]

U-pipe Borehole Heat Exchangers (BHE) are widely used today in ground source heating and cooling systems in spite of their less than optimal performance. This thesis provides a better understanding on the function of U-pipe BHEs and Investigates alternative methods to reduce the temperature difference between the circulating fluid and the borehole wall, including one thermosyphon and three different types of coaxial BHEs.

Field tests are performed using distributed temperature measurements along U-pipe and coaxial heat exchangers installed in groundwater filled boreholes. The measurements are carried out during heat injection thermal response tests and during short heat extraction periods using heat pumps. Temperatures are measured inside the secondary fluid path, in the groundwater, and at the borehole wall. These type of temperature measurements were until now missing.

A new method for testing borehole heat exchangers, Distributed Thermal Response Test (DTRT), has been proposed and demonstrated in U-pipe, pipe-in-pipe, and multi-pipe BHE designs. The method allows the quantification of the BHE performance at a local level.

The operation of a U-pipe thermosyphon BHE consisting of an insulated down-comer and a larger riser pipe using CO2 as a secondary fluid has been demonstrated in a groundwater filled borehole, 70 m deep. It was found that the CO2 may be sub-cooled at the bottom and that it flows upwards through the riser in liquid state until about 30 m depth, where it starts to evaporate.

Various power levels and different volumetric flow rates have been imposed to the tested BHEs and used to calculate local ground thermal conductivities and thermal resistances. The local ground thermal conductivities, preferably evaluated at thermal recovery conditions during DTRTs, were found to vary with depth. Local and effective borehole thermal resistances in most heat exchangers have been calculated, and their differences have been discussed in an effort to suggest better methods for interpretation of data from field tests.

Large thermal shunt flow between down- and up-going flow channels was identified in all heat exchanger types, particularly at low volumetric flow rates, except in a multi-pipe BHE having an insulated central pipe where the thermal contact between down- and up-coming fluid was almost eliminated.

At relatively high volumetric flow rates, U-pipe BHEs show a nearly even distribution of the heat transfer between the ground and the secondary fluid along the depth. The same applies to all coaxial BHEs as long as the flow travels downwards through the central pipe. In the opposite flow direction, an uneven power distribution was measured in multi-chamber and multi-pipe BHEs.

Pipe-in-pipe and multi-pipe coaxial heat exchangers show significantly lower local borehole resistances than U-pipes, ranging in average between 0.015 and 0.040 Km/W. These heat exchangers can significantly decrease the temperature difference between the secondary fluid and the ground and may allow the use of plain water as secondary fluid, an alternative to typical antifreeze aqueous solutions. The latter was demonstrated in a pipe-in-pipe BHE having an effective resistance of about 0.030 Km/W.

Forced convection in the groundwater achieved by injecting nitrogen bubbles was found to reduce the local thermal resistance in U-pipe BHEs by about 30% during heat injection conditions. The temperatures inside the groundwater are homogenized while injecting the N2, and no radial temperature gradients are then identified. The fluid to groundwater thermal resistance during forced convection was measured to be 0.036 Km/W. This resistance varied between this value and 0.072 Km/W during natural convection conditions in the groundwater, being highest during heat pump operation at temperatures close to the water density maximum.

Place, publisher, year, edition, pages
Stockholm: KTH Royal Institute of Technology, 2013. p. 138
Series
Trita-REFR, ISSN 1102-0245 ; 13:01
Keywords
Borehole heat exchangers, Distributed Thermal Response Test, Ground Source Heat Pumps, Coaxial, U-pipe, Multi-pipe, Pipe-in-pipe, Multi-chamber, Groundwater, Thermosyphon
National Category
Energy Systems Mineral and Mine Engineering Geotechnical Engineering Construction Management Energy Engineering Geophysical Engineering Other Civil Engineering
Research subject
SRA - Energy
Identifiers
urn:nbn:se:kth:diva-117746 (URN)978-91-7501-626-9 (ISBN)
Public defence
2013-02-22, D3, Lindstedtsvägen 5, KTH, Stockholm, 10:00 (English)
Opponent
Supervisors
Projects
EFFSYS+EFFSYS2
Funder
The Swedish Energy AgencyStandUp
Note

QC 20130204

Available from: 2013-02-04 Created: 2013-02-04 Last updated: 2022-06-24Bibliographically approved

Open Access in DiVA

No full text in DiVA

Other links

Publisher's full textScopusPublished version

Authority records

Acuña, JoséPalm, Björn

Search in DiVA

By author/editor
Acuña, JoséPalm, Björn
By organisation
Applied Thermodynamics and Refrigeration
In the same journal
HVAC & R RESEARCH
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar

doi
urn-nbn

Altmetric score

doi
urn-nbn
Total: 1593 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf