A management system for the electrical network of the french parliament building
KTH, School of Electrical Engineering (EES), Automatic Control.
2007 (English)Independent thesis Advanced level (professional degree), 20 credits / 30 HE creditsStudent thesis
Abstract [en]

This report describes an exemple of management systems based on Programmable Logic Controllers. Such systems are designed in order to help monitoring and controlling of a physical system. The system which is controlled in this project is the electrical network of two buildings used by the french parliament. This network consists of several electrical boards where each board is made up of several circuit breakers that protect the electrical equipments and other boards. The goal of the management system is to monitor the network, i.e acquire data about the state of the network, and to control the network, i.e control the position of the breakers (open/closed) according to power supplies availability and network load.

The management system is based on a multiple levels structure.

- Level 0 : is the operating part of the network which is made up of sensors and actuators.

- Level 1 : is the part made up of the Programmable Logic Controllers (PLC). The sensorsĀ and actuators of the level 0 are directly connected to the PLC.

- Level 2 : This level enables to acquire the information on a computer and to monitor/control it through an ergonomic graphical interface. Thanks to that level, the operator can keep an eye on the network remotely and control it.

This project consists in programming the Programmable Logic Controllers, and the Human

Machine Interface, according to the specifications of the customer. Only a part of the system has so far been developped since the total duration of the project is about 2 years. The main functions of the PLC program has been programmed, and tested successfully but not in real conditions since the buildings were still under construction. Simulation tools were used in order to test Modbus communication between the levels 0 and 1. The function that controls the breakers according to power supplies availability has been tested as well, by forcing variables in the PLC (to simulate a voltage loss for example).

Place, publisher, year, edition, pages
2007. , 43 p.
National Category
Control Engineering
Identifiers
URN: urn:nbn:se:kth:diva-106242OAI: oai:DiVA.org:kth-106242DiVA: diva2:573439
Subject / course
Automatic Control
Educational program
Master of Science in Engineering
Uppsok
Technology
Examiners
Available from: 2012-12-03 Created: 2012-11-30 Last updated: 2012-12-03Bibliographically approved

Open Access in DiVA

fulltext(1836 kB)292 downloads
File information
File name FULLTEXT01.pdfFile size 1836 kBChecksum SHA-512
b073e9f005ea4ce2db26158b4683fb031cf2a4725866c0255658c723f0087dddbcc69d89414c1e763511cccc5e1cbd7cdcc306553a9468a394616e2aab8c7a4d
Type fulltextMimetype application/pdf

By organisation
Automatic Control
Control Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 292 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 756 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard1
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf