An Approach for Optimal Placement of SVC to Minimize Load Curtailment
KTH, School of Electrical Engineering (EES), Electric Power Systems.
2009 (English)Independent thesis Advanced level (professional degree), 20 credits / 30 HE creditsStudent thesis
Abstract [en]

Modern electric power system is very complex and undergoes unforeseen rapid changes in terms of demand/generation patterns and trading activities that hinder the system security. For example, a steep rise in load or a certain critical line/equipment outage can cause line overload or undesirable voltage profile and such events can push the system towards instability and possibly even a black out. In order to cope with such situations, it is common practice to purchase the rights of asking for a reduction of load from certain customers. However, it is not an ideal situation from reliability perspective, financial as well as having critical load in the power system. Load curtailment is the collection of control strategies employed to reduce the electric power loading in the system and main aim is to push the disturbed system towards a new equilibrium state. Load curtailment may be required even when voltages at some buses are out of their safe operating limits, to prevent a possible voltage collapse.

Flexible AC Transmission Systems (FACTS) controllers could be a suitable alternative to provide reactive power support at the load centres locally and hence keep the voltages within their safe operating limits. Due to high costs of FACTS devices, their proper location in the system must be ascertained.

To deal with the above problem a new methodology has been proposed, in this thesis, in terms of sensitivity factors for the optimal location of Static Var Compensator (SVC) to minimize the system load curtailment requirements for maintaining the system security. In this work, SVC has been considered for the study to minimize the load curtailment. The effectiveness of the proposed method has been tested on IEEE 14-bus and practical 75-bus Indian systems. Optimal placement have been obtained for the base case loading and to verify its locations, an Optimal Power Flow (OPF) problem has been formulated with an objective to minimize the load curtailment and satisfying all operating constraints along with optimal settings of SVC which is used at suggested places from developed methodology. Moreover, the effects of SVC on load curtailment reduction, which are located at base case loading, have also been investigated for different operating conditions e.g., increased load or having different contractual obligation in the system.

Place, publisher, year, edition, pages
2009. , 63 p.
EES Examensarbete / Master Thesis
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
URN: urn:nbn:se:kth:diva-119238OAI: diva2:610050
Educational program
Master of Science in Engineering - Electrical Engineering
Available from: 2013-03-12 Created: 2013-03-08 Last updated: 2013-03-12Bibliographically approved

Open Access in DiVA

fulltext(570 kB)804 downloads
File information
File name FULLTEXT01.pdfFile size 570 kBChecksum SHA-512
Type fulltextMimetype application/pdf

By organisation
Electric Power Systems
Electrical Engineering, Electronic Engineering, Information Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 804 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 224 hits
ReferencesLink to record
Permanent link

Direct link