Experimental Validation of a Numerical Model for the Thermal Response of a Borehole Field
KTH, School of Industrial Engineering and Management (ITM), Energy Technology.ORCID iD: 0000-0002-5093-9070
KTH, School of Industrial Engineering and Management (ITM), Energy Technology.
KTH, School of Industrial Engineering and Management (ITM), Energy Technology.ORCID iD: 0000-0002-3490-1777
Instituto de Ingenieria Energetica, Universitat Politecnica de Valencia.
2014 (English)In: ASHRAE TRANSACTIONS 2014, VOL 120, PT 2, ASHRAE , 2014, Vol. 120, no 2Conference paper (Refereed)
Abstract [en]

The design of borehole fields for ground coupled-heat pump systems is often based on so-called g-functions, a pre-calculated dimensionless temperature response to a step heat load. The g-function is specific to the borehole field geometry. For a long-term analysis of a particular borehole field, the average borehole wall temperature is obtained from the g-function and a temporal superposition of its thermal load steps. There are two accepted provisions for the g-function regarding the boundary condition used at (and along) the borehole wall: a constant heat flux at every instant of time, or a uniform temperature at constant total heat flow to the borehole field, respectively. In this paper, a numerical model is built up according to the geometrical characteristics and ground thermal properties of a 2x3 borehole demo site at the Universitat Politecnica de Valencia, Spain. The model is separately studied with regard to the two boundary conditions. The models are first compared in terms of their g-function, which are verified against reference solutions. Then, the daily fluid temperatures are obtained from each of these models with measured daily loads during a six year period. The results are compared with measured daily fluid temperatures for the sixth year of operation. The simulated values present, in general, a good agreement with the measured data. The results show that there are no significant differences with regard to the boundary conditions at the borehole wall, which for this specific case is due to the fact that the system is thermally balanced. The simulated temperatures are more accurate during cooling periods.

Place, publisher, year, edition, pages
ASHRAE , 2014. Vol. 120, no 2
National Category
Energy Engineering
URN: urn:nbn:se:kth:diva-159054ISI: 000346573500047OAI: diva2:782696
ASHRAE Annual Conference, APR 16, 2014, Seattle, WA, USA

QC 20150122

Available from: 2015-01-22 Created: 2015-01-20 Last updated: 2016-04-20Bibliographically approved

Open Access in DiVA

fulltext(344 kB)9 downloads
File information
File name FULLTEXT01.pdfFile size 344 kBChecksum SHA-512
Type fulltextMimetype application/pdf

Search in DiVA

By author/editor
Monzó, PatriciaRuiz-Calvo, FelixAcuna, Jose
By organisation
Energy Technology
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 9 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 174 hits
ReferencesLink to record
Permanent link

Direct link