Development and application of high voltage dielectric spectroscopy for diagnosis of medium voltage XLPE cables
KTH, Superseded Departments, Electrical Systems.
2001 (English)Doctoral thesis, monograph (Other scientific)
Abstract [en]

When polymer power cables were introduced into mediumvoltage applications in the late 1960s, the degradationphenomenon later referred to aswater treeingwas still unknown. However, this changedwithin a relatively short space of time. Just 5-10 years afterthese first polymer applications, faults began to appear thatcould be attributed to the new phenomenon-water treeing. Sincethen, cable manufacturers have been improving their designsgradually, and cables produced today are assumed to have muchlower susceptibility to water trees. However, water treeing isstill assumed to be the most important degradation process inthese applications.

There are huge amounts of polymer cable installations thatare degraded by water trees. Since many of these cables areinstalled in the same grid nets, one cable fault oftengenerates another. If two or more cables fail at the same time,the consequences can be extensive. A non-destructive diagnosticmethod makes it possible to assess cables and take action priorto failures.

This thesis presents the results of research work on thedevelopment of a measurement technique and diagnostic methodfor the assessment of medium voltage XLPE cables in the field.The method used is called high voltage dielectric spectroscopy,and involves the measurement of capacitance and loss as afunction of frequency at high voltages. The method is used in ashort frequency range of approximately one decade in thelow-frequency region (normally from 1 down to 0.1 Hz). Thevoltage levels used initially are all below the service-voltagelevel. If the cable is assessed to be free from water trees, aslightly increased voltage can be used.

Based on dielectric-spectroscopy measurements, specificwater-tree analysis and breakdown tests, a set of measurementprocedures and criteria that take into account differences incable designs has been proposed for the assessment of mediumvoltage XLPE cables. The characteristic responses of XLPEcables (in both non and water-tree-deteriorated cases) make itpossible to separate the cable response from the influence ofaccessories. Field experience shows thatwater-tree-deteriorated cables with relatively low breakdownstrengths can remain in service for many years.

Keywords:dielectric spectroscopy, high voltage,variable frequency, diagnostics, non-destructive diagnostics,cables, medium voltage, polymer, XLPE, water trees, watertreeing

Place, publisher, year, edition, pages
Stockholm: Elektrotekniska system , 2001. , ix, 202 p.
Trita-ETS, ISSN 1650-674X ; 2001:02
Keyword [en]
dielectric spectroscopy, high voltage, variable frequency, diagnostics, non-disgnostics
URN: urn:nbn:se:kth:diva-3278OAI: diva2:9062
Public defence
NR 20140805Available from: 2001-12-18 Created: 2001-12-18Bibliographically approved

Open Access in DiVA

fulltext(4250 kB)7870 downloads
File information
File name FULLTEXT01.pdfFile size 4250 kBChecksum SHA-1
Type fulltextMimetype application/pdf

By organisation
Electrical Systems

Search outside of DiVA

GoogleGoogle Scholar
Total: 7870 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 1286 hits
ReferencesLink to record
Permanent link

Direct link