Baudoin, A., Hatsagi, B., Alvarez, M., Ängquist, L., Nee, S., Norrga, S. & Modeer, T. (2019). Experimental results from a Thomson-coil actuator for a vacuum interrupter in an HVDC breaker. The Journal of Engineering (17), 3527-3531
Open this publication in new window or tab >>Experimental results from a Thomson-coil actuator for a vacuum interrupter in an HVDC breaker
Show others...
2019 (English)In: The Journal of Engineering, E-ISSN 2051-3305, no 17, p. 3527-3531Article in journal (Refereed) Published
Abstract [en]

Recent developments in high-voltage direct current transmission technology and the plans for multi-terminals motivate research efforts on the fast DC breaker. A novel concept to interrupt current up to several kiloamperes within a few milliseconds is presently under development, using a vacuum interrupter together with power electronics to create an artificial zero-crossing in the current through the switch. To achieve this objective, one critical component in the concept is an ultra-fast linear mechanical actuator. A prototype has been developed based on a Thomson coil. The experimental results are presented and show how a contact gap in a vacuum interrupter was effectively created in a controlled manner. Current of several kiloamperes was successfully interrupted within 3ms, thanks to the high-speed operation of the linear actuator.

Place, publisher, year, edition, pages
INST ENGINEERING TECHNOLOGY-IET, 2019
Keywords
vacuum interrupters, HVDC power transmission, experimental results, Thomson-coil actuator, vacuum interrupter, HVDC breaker, high-voltage direct current transmission technology, fast DC breaker, linear actuator, ultrafast linear mechanical actuator
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
urn:nbn:se:kth:diva-284620 (URN)10.1049/joe.2018.8219 (DOI)000472719600012 ()
Note

QC 20201118

Available from: 2020-11-01 Created: 2020-11-01 Last updated: 2024-04-05Bibliographically approved
Zhang, H., Hasler, J.-P. -., Johansson, N., Ängquist, L. & Nee, H.-P. (2017). Frequency response improvement with synchronous condenser and power electronics converters. In: 2017 IEEE 3rd International Future Energy Electronics Conference and ECCE Asia, IFEEC - ECCE Asia 2017: . Paper presented at 3rd IEEE International Future Energy Electronics Conference and ECCE Asia, IFEEC - ECCE Asia 2017, Kaohsiung, Taiwan, 3 June 2017 through 7 June 2017 (pp. 1002-1007). Institute of Electrical and Electronics Engineers (IEEE), Article ID 7992178.
Open this publication in new window or tab >>Frequency response improvement with synchronous condenser and power electronics converters
Show others...
2017 (English)In: 2017 IEEE 3rd International Future Energy Electronics Conference and ECCE Asia, IFEEC - ECCE Asia 2017, Institute of Electrical and Electronics Engineers (IEEE), 2017, p. 1002-1007, article id 7992178Conference paper, Published paper (Refereed)
Abstract [en]

This paper gives an overall review of the working principle of the inertial response from the synchronous condenser for frequency support in the grid. In addition to this, four proposed frequency control strategies for improvement of network frequency response by static energy storage devices, such as the Static Synchronous Compensator (STATCOM) with suitable energy storage elements or the battery energy storage system (BESS), are presented. The proposed frequency control strategies are evaluated and benchmarked with the synchronous condenser in the same network. It is shown that a power electronic converter based system with energy storage can be designed with lower rating, still providing the same or better frequency support than the synchronous condenser.

Place, publisher, year, edition, pages
Institute of Electrical and Electronics Engineers (IEEE), 2017
National Category
Energy Systems
Identifiers
urn:nbn:se:kth:diva-223037 (URN)10.1109/IFEEC.2017.7992178 (DOI)000426696300177 ()2-s2.0-85034074684 (Scopus ID)9781509051571 (ISBN)
Conference
3rd IEEE International Future Energy Electronics Conference and ECCE Asia, IFEEC - ECCE Asia 2017, Kaohsiung, Taiwan, 3 June 2017 through 7 June 2017
Note

QC 20180214

Available from: 2018-02-14 Created: 2018-02-14 Last updated: 2024-03-18Bibliographically approved
Zhang, H., Ängquist, L., Norrga, S., Nee, H.-P. & Östlund, S. (2016). Benchmark of high-power STATCOM topologies for flicker compensation. In: 2016 18TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'16 ECCE EUROPE): . Paper presented at 18th European Conference on Power Electronics and Applications (EPE), SEP 05-09, 2016, GERMANY. IEEE
Open this publication in new window or tab >>Benchmark of high-power STATCOM topologies for flicker compensation
Show others...
2016 (English)In: 2016 18TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'16 ECCE EUROPE), IEEE, 2016Conference paper, Published paper (Refereed)
Abstract [en]

The current from an electrical arc furnace (EAF) in a steel plant is highly unsymmetrical, i.e. it comprises a large amount of negative sequence. This causes problems with the voltage stability in the capacitor submodules for a static synchronous compensator (STATCOM), when implemented using the modular multilevel converter (M2C) concept. In order to counteract the uncontrollability of the capacitor voltage, a common practice is to circulate a zero-sequence fundamental current or a direct current. The method brings the benefit of re-balancing the active power among the individual phases while it requires over-rating of the valve current or dc voltage of the STATCOM. This would in practice give a more expensive design. This paper presents a benchmark of various M2C-based STATCOM designs considering the valve overrating. The STATCOM topologies will be benchmarked with the EAF modeled for all possible combinations of positive-and negative-sequence current. The rating comparison considering the dc capacitor ripple and zero-sequence harmonic injection are discussed.

Place, publisher, year, edition, pages
IEEE, 2016
Series
European Conference on Power Electronics and Applications, ISSN 2325-0313
Keywords
Static Synchronous Compensator (STATCOM), Multilevel Converters
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
urn:nbn:se:kth:diva-197014 (URN)10.1109/EPE.2016.7695478 (DOI)000386637300227 ()2-s2.0-84996791605 (Scopus ID)
Conference
18th European Conference on Power Electronics and Applications (EPE), SEP 05-09, 2016, GERMANY
Note

QC 20161209

Available from: 2016-12-09 Created: 2016-11-28 Last updated: 2024-03-15Bibliographically approved
Ahmed, N., Ängquist, L., Mehmood, S., Antonopoulos, A., Harnefors, L., Norrga, S. & Nee, H.-P. (2016). Efficient Modeling of an MMC-Based Multiterminal DC System Employing Hybrid HVDC Breakers. In: 2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM): . Paper presented at IEEE-Power-and-Energy-Society General Meeting (PESGM), JUL 17-21, 2016, Boston, MA. IEEE
Open this publication in new window or tab >>Efficient Modeling of an MMC-Based Multiterminal DC System Employing Hybrid HVDC Breakers
Show others...
2016 (English)In: 2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM), IEEE , 2016Conference paper, Published paper (Refereed)
Place, publisher, year, edition, pages
IEEE, 2016
Series
IEEE Power and Energy Society General Meeting PESGM, ISSN 1944-9925
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
urn:nbn:se:kth:diva-209094 (URN)000399937902157 ()978-1-5090-4168-8 (ISBN)
Conference
IEEE-Power-and-Energy-Society General Meeting (PESGM), JUL 17-21, 2016, Boston, MA
Note

QC 20170619

Available from: 2017-06-19 Created: 2017-06-19 Last updated: 2024-03-18Bibliographically approved
Leterme, W., Ahmed, N., Beerten, J., Ängquist, L., Van Hertem, D. & Norrga, S. (2015). A new HVDC grid test system for HVDC grid dynamics and protection studies in EMT-type software. In: IET Seminar Digest: . Paper presented at 11th IET International Conference on AC and DC Power Transmission, 10 February 2015 through 12 February 2015. Institution of Engineering and Technology (CP654)
Open this publication in new window or tab >>A new HVDC grid test system for HVDC grid dynamics and protection studies in EMT-type software
Show others...
2015 (English)In: IET Seminar Digest, Institution of Engineering and Technology, 2015, no CP654Conference paper, Published paper (Refereed)
Abstract [en]

This paper proposes a new HVDC grid test system for electro-magnetic transient analysis, suitable for HVDC power system studies ranging from protection to dynamic studies investigating converter behaviour and interactions. In the recent past research interest in HVDC grids has increased, leading to a multitude of studies concerning dc power flow and optimal power flow, dynamics and HVDC grid protection. However, each of these studies makes use of different grid topologies, configurations and transmission line parameters. In this paper, a standard HVDC grid test system is proposed and an implementation in EMT-type software is provided. The implementation in EMT-type software makes use of a frequency dependent cable model, continuous converter model and a reduced dc breaker model. By means of a protection study, the effectiveness and computational efficiency of the proposed HVDC grid test system is demonstrated. The model with its parameters will be made publicly available.

Place, publisher, year, edition, pages
Institution of Engineering and Technology, 2015
Keywords
Electromagnetic transient simulation, HVDC grid, Power system fault, Power system protection, Test system, Computational efficiency, DC power transmission, Electric load flow, Electric power transmission, Electric power transmission networks, HVDC power transmission, Software testing, Testing, Transient analysis, Test systems, Electric power system protection
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
urn:nbn:se:kth:diva-175093 (URN)10.1049/cp.2015.0068 (DOI)2-s2.0-84939229610 (Scopus ID)
Conference
11th IET International Conference on AC and DC Power Transmission, 10 February 2015 through 12 February 2015
Funder
StandUp
Note

QC 20151211

Available from: 2015-12-11 Created: 2015-10-09 Last updated: 2024-03-18Bibliographically approved
Ahmed, N., Ängquist, L., Mahmood, S., Antonopoulos, A., Harnefors, L., Norrga, S. & Nee, H.-P. (2015). Efficient Modeling of an MMC-Based Multiterminal DC System Employing Hybrid HVDC Breakers. IEEE Transactions on Power Delivery, 30(4), 1792-1801
Open this publication in new window or tab >>Efficient Modeling of an MMC-Based Multiterminal DC System Employing Hybrid HVDC Breakers
Show others...
2015 (English)In: IEEE Transactions on Power Delivery, ISSN 0885-8977, E-ISSN 1937-4208, Vol. 30, no 4, p. 1792-1801Article in journal (Refereed) Published
Abstract [en]

The feasibility of future multiterminal dc (MTDC) systems depends largely on the capability to withstand dc-side faults. Simulation models of MTDC systems play a very important role in investigating these faults. For such studies, the test system needs to be accurate and computationally efficient. This paper proposes a detailed equivalent model of the modular multilevel converter (MMC), which is used to develop the MTDC test system. The proposed model is capable of representing the blocked-mode operation of the MMC, and can be used to study the balancing control of the capacitor voltages. In addition, the operation of the MMC when redundant submodules are included in the arms can also be studied. A simplified model of a hybrid high-voltage dc breaker is also developed. Hence, the developed test system is capable of accurately describing the behavior of the MMC-based MTDC system employing hybrid HVDC breakers, during fault conditions. Using time-domain simulations, permanent dc-side faults are studied in the MTDC system. In addition, a scheme to control the fault current through the MMC using thyristors on the ac side of the converter is proposed.

Place, publisher, year, edition, pages
IEEE, 2015
Keywords
DC-side faults, HVDC breaker, HVDC transmission, modeling, modular multilevel converter (MMC)
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Research subject
SRA - Energy
Identifiers
urn:nbn:se:kth:diva-172681 (URN)10.1109/TPWRD.2015.2398825 (DOI)000358503900017 ()2-s2.0-84937948815 (Scopus ID)
Funder
StandUp
Note

QC 20150901

Available from: 2015-09-01 Created: 2015-08-27 Last updated: 2024-03-18Bibliographically approved
Gregoire, L.-A., Blanchette, H. F., Li, W., Antonopoulos, A., Ängquist, L. & Al-Haddad, K. (2015). Modular Multilevel Converters Overvoltage Diagnosis and Remedial Strategy During Blocking Sequences. IEEE transactions on power electronics, 30(5), 2777-2785
Open this publication in new window or tab >>Modular Multilevel Converters Overvoltage Diagnosis and Remedial Strategy During Blocking Sequences
Show others...
2015 (English)In: IEEE transactions on power electronics, ISSN 0885-8993, E-ISSN 1941-0107, Vol. 30, no 5, p. 2777-2785Article in journal (Refereed) Published
Abstract [en]

In this paper, the authors first highlight an existing overvoltage phenomenon that is inherent to the modular multilevel converter (MMC) topology. The latter occurs during the blocking sequences of semiconductor devices if the converter needs to be stopped due to circulating current, loss of control, or unexpected faults. An analysis based on time-domain expressions describing each operating sequence during normal and faulty blocking conditions is used to demonstrate the origin of this overvoltage. Thereafter, system behaviour is obtained when devices gating signals are withheld as well as the exact overvoltage cause. Real-time simulation, with submicrosecond time steps, and experimental results validate the overvoltage phenomena and the proposed remedial strategy to avoid uncontrolled faulty conditions.

Keywords
Fault diagnosis, HVDC, modular multilevel converters, overvoltage, PWM, real-time simulation
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
urn:nbn:se:kth:diva-159346 (URN)10.1109/TPEL.2014.2357674 (DOI)000346980000038 ()2-s2.0-84920123984 (Scopus ID)
Note

QC 20150202

Available from: 2015-02-02 Created: 2015-01-29 Last updated: 2024-03-15Bibliographically approved
Antonopoulos, A., Ängquist, L., Harnefors, L. & Nee, H.-P. (2015). Optimal Selection of the Average Capacitor Voltage for Variable-Speed Drives With Modular Multilevel Converters. IEEE transactions on power electronics, 30(1), 227-234
Open this publication in new window or tab >>Optimal Selection of the Average Capacitor Voltage for Variable-Speed Drives With Modular Multilevel Converters
2015 (English)In: IEEE transactions on power electronics, ISSN 0885-8993, E-ISSN 1941-0107, Vol. 30, no 1, p. 227-234Article in journal (Refereed) Published
Abstract [en]

Variable-speed drives have reduced voltage requirementswhen operating below the base speed. In a modularmultilevel-converter-based (M2C-based) motor drive it is thenpossible to operate with reduced voltage in the submodulecapacitors, than at the base speed. In this sense, a greatercapacitor-voltage ripple can be accommodated, without exceedingthe maximum peak-capacitor voltage. This paper presents ananalytical investigation for the optimal selection of the averagecapacitor voltage for M2Cs, when the motor is operating withrated torque, below the base speed. This method does not requireany power exchange between the converter arms, so it keepsthe conduction losses at the minimum level. Additionally, themethod decreases the switching losses, due to the decreasedcapacitor-voltage level. The overall ratings of the converterremain the same as in the base-speed operation. It is shownthat this method can be applied at a speed range betweenthe base speed and down to approximately one third of it,i.e, an operating range that covers the requirements for typicalpump- and fan-type applications. The results obtained from theanalytical investigation are experimentally verified on a downscaledlaboratory prototype M2C.

Keywords
Capacitor-voltage control, medium-power variable-speed drives, modular multilevel converters, optimization.
National Category
Other Electrical Engineering, Electronic Engineering, Information Engineering
Research subject
Electrical Engineering
Identifiers
urn:nbn:se:kth:diva-156198 (URN)10.1109/TPEL.2014.2316273 (DOI)000341624200019 ()2-s2.0-84906809639 (Scopus ID)
Note

QC 20141201

Available from: 2014-11-24 Created: 2014-11-24 Last updated: 2024-03-15Bibliographically approved
Ahmed, N., Ängquist, L., Antonopoulos, A., Harnefors, L., Norrga, S. & Nee, H.-P. (2015). Performance of the modular multilevel converter with redundant submodules. In: IECON 2015 - 41st Annual Conference of the IEEE Industrial Electronics Society: . Paper presented at 41st Annual Conference of the IEEE Industrial Electronics Society, IECON 2015, Pacifico YokohamaYokohama, Japan, 9 November 2015 through 12 November 2015 (pp. 3922-3927). Institute of Electrical and Electronics Engineers (IEEE), Article ID 7392712.
Open this publication in new window or tab >>Performance of the modular multilevel converter with redundant submodules
Show others...
2015 (English)In: IECON 2015 - 41st Annual Conference of the IEEE Industrial Electronics Society, Institute of Electrical and Electronics Engineers (IEEE), 2015, p. 3922-3927, article id 7392712Conference paper, Published paper (Refereed)
Abstract [en]

The modular multilevel converter (MMC) is the state-of-the-art voltage-source converter (VSC) topology used for various power-conversion applications. In the MMC, submodule failures can occur due to various reasons. Therefore, additional submodules called the redundant submodules are included in the arms of the MMC to fulfill the fault-safe operation requirement. The performance of the MMC with redundant submodules has not been widely covered in the published literature. This paper investigates the performance of the MMC with redundant submodules in the arms. Two different control strategies are used and compared for integrating redundant submodules. The response of the MMC to a submodule failure for the two strategies is also studied. Moreover, the operation of the MMC with redundant submodules is validated experimentally using the converter prototype in the laboratory.

Place, publisher, year, edition, pages
Institute of Electrical and Electronics Engineers (IEEE), 2015
Keywords
Modular multilevel converter, redundancy
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Research subject
SRA - Energy
Identifiers
urn:nbn:se:kth:diva-185746 (URN)10.1109/IECON.2015.7392712 (DOI)000382950703162 ()2-s2.0-84973163763 (Scopus ID)9781479917624 (ISBN)
Conference
41st Annual Conference of the IEEE Industrial Electronics Society, IECON 2015, Pacifico YokohamaYokohama, Japan, 9 November 2015 through 12 November 2015
Funder
StandUp
Note

QC 20161104

Available from: 2016-04-26 Created: 2016-04-26 Last updated: 2024-03-15Bibliographically approved
Hassanpoor, A., Ängquist, L., Norrga, S., Ilves, K. & Nee, H.-P. (2015). Tolerance band modulation methods for modular multilevel converters. IEEE transactions on power electronics, 30(1), 311-326, Article ID 6739183.
Open this publication in new window or tab >>Tolerance band modulation methods for modular multilevel converters
Show others...
2015 (English)In: IEEE transactions on power electronics, ISSN 0885-8993, E-ISSN 1941-0107, Vol. 30, no 1, p. 311-326, article id 6739183Article in journal (Refereed) Published
Abstract [en]

Modular multilevel converters (M2Cs) are increasingly used in high-voltage direct current (HVDC) systems. The efficiency of M2Cs is influenced by the modulation and cell selecting methods, which determines the switching frequency and capacitor voltage ripple in the converter station. A new approach to modulation of the M2C is presented in this paper. Tolerance band methods are employed to obtain the switching instants, and also cell selection. The proposed methods overcome the modulation problem for converters with few cells on one hand and also reduce the sorting efforts for cell balancing purposes of many cells converter on the other hand. Three different algorithms are also proposed to balance the cell capacitor voltages. The evaluation is done in time-domain simulation by which the performance of each method is studied in both the steady-state and transient cases. It is observed that using tolerance band methods not only reduces the switching frequency but also allows for handling severe fault cases in a grid-connected system. Eventually, the most promising tolerance band method has been implemented and verified in a real-time digital simulator, RTDS®. The average switching frequency of 70 Hz has been achieved for the system under study, while the capacitor voltage ripple is limited to 10% of the nominal cell voltage.

Place, publisher, year, edition, pages
IEEE, 2015
Keywords
High-voltage direct current transmission, power conversion, real-time systems, switching frequency, switching loss
National Category
Other Electrical Engineering, Electronic Engineering, Information Engineering
Research subject
SRA - Energy
Identifiers
urn:nbn:se:kth:diva-166885 (URN)10.1109/TPEL.2014.2305114 (DOI)000341624200026 ()2-s2.0-84906748780 (Scopus ID)
Funder
StandUp
Note

QC 20150609

Available from: 2015-06-09 Created: 2015-05-21 Last updated: 2024-03-18Bibliographically approved
Organisations
Identifiers
ORCID iD: ORCID iD iconorcid.org/0000-0002-6362-6030

Search in DiVA

Show all publications