kth.sePublications KTH
Change search
Link to record
Permanent link

Direct link
Publications (10 of 23) Show all publications
Bi, Y., Hu, N., Sadeghian, P., Sadrizadeh, S., Asuero Von Munthe Af Morgenstierne, M., Mathisen, H. M., . . . Cao, G. (2025). Numerical study on the application of low-turbulence air curtain surrounding laminar airflow distribution in operating rooms. Building Simulation, 18(3), 601-617
Open this publication in new window or tab >>Numerical study on the application of low-turbulence air curtain surrounding laminar airflow distribution in operating rooms
Show others...
2025 (English)In: Building Simulation, ISSN 1996-3599, E-ISSN 1996-8744, Vol. 18, no 3, p. 601-617Article in journal (Refereed) Published
Abstract [en]

Laminar airflow (LAF) is essential for maintaining a sterile environment in operating rooms, but its rapid unidirectional flow decay leads to low airflow efficiency and increases energy consumption. The objective of this study is to investigate the energy-saving and air quality benefits of using a low-turbulence air curtain around laminar airflow, which is referred to as protective laminar airflow (PLAF). Numerical simulations were used to model airflow and particle transport, and a series of experiments were conducted in a real operating room at St. Olavs Hospital, Norway, to validate the simulation results. The findings indicate that when the unidirectional airflow supply velocity is maintained at 0.25 m/s, combined with an air curtain that has the width of 2 cm and the velocity of 1.5 m/s, the PLAF system outperforms the conventional LAF system operating at a unidirectional airflow supply velocity of 0.30 m/s. This configuration results in a 17.3% energy saving, showing the potential of this airflow distribution strategy to enhance both cleanliness and energy efficiency.

Place, publisher, year, edition, pages
Springer Nature, 2025
National Category
Engineering and Technology
Identifiers
urn:nbn:se:kth:diva-370672 (URN)10.1007/s12273-024-1229-7 (DOI)001396187900001 ()2-s2.0-105001084500 (Scopus ID)
Note

QC 20251003

Available from: 2025-09-29 Created: 2025-09-29 Last updated: 2025-10-06Bibliographically approved
Grosse, L., Saeidian, S., Sadeghian, P., Oechtering, T. J. & Skoglund, M. (2024). Quantifying Privacy via Information Density. In: 2024 IEEE International Symposium on Information Theory, ISIT 2024 - Proceedings: . Paper presented at 2024 IEEE International Symposium on Information Theory, ISIT 2024, July 7-12, 2024, Athens, Greece (pp. 3071-3076). Institute of Electrical and Electronics Engineers (IEEE)
Open this publication in new window or tab >>Quantifying Privacy via Information Density
Show others...
2024 (English)In: 2024 IEEE International Symposium on Information Theory, ISIT 2024 - Proceedings, Institute of Electrical and Electronics Engineers (IEEE) , 2024, p. 3071-3076Conference paper, Published paper (Refereed)
Abstract [en]

We examine the relationship between privacy metrics that utilize information density to measure information leakage between a private and a disclosed random variable. Firstly, we prove that bounding the information density from above or below in turn implies a lower or upper bound on the information density, respectively. Using this result, we establish new relationships between local information privacy, asymmetric local information privacy, pointwise maximal leakage and local differential privacy. We further provide applications of these relations to privacy mechanism design. Secondly, we provide equivalence statements of lower bounds on information density and risk-averse adversaries. More specifically, we prove an equivalence between a guessing framework and a cost-function framework that both result in the same lower bound on the information density.

Place, publisher, year, edition, pages
Institute of Electrical and Electronics Engineers (IEEE), 2024
National Category
Computer Sciences
Identifiers
urn:nbn:se:kth:diva-353520 (URN)10.1109/ISIT57864.2024.10619510 (DOI)001304426903036 ()2-s2.0-85202889092 (Scopus ID)
Conference
2024 IEEE International Symposium on Information Theory, ISIT 2024, July 7-12, 2024, Athens, Greece
Note

Part of ISBN: 9798350382846

QC 20240924

Available from: 2024-09-19 Created: 2024-09-19 Last updated: 2025-12-08Bibliographically approved
Sadeghian, P. & Sadrizadeh, S. (2022). Assessment of diffuse ceiling ventilation performance on transmission of airborne infectious diseases. In: : . Paper presented at Indoor Air 2022 the 17th International Conference on Indoor Air Quality and Climate, June 12th to 16th Kuopio, Finland. International Society of Indoor Air Quality and Climate
Open this publication in new window or tab >>Assessment of diffuse ceiling ventilation performance on transmission of airborne infectious diseases
2022 (English)Conference paper, Published paper (Refereed)
Abstract [en]

Ventilation systems have been widely used to satisfy the occupants' indoor air quality and thermally comfort conditions. Various air distribution systems have been developed to supply clean air, including mixing, displacement, and diffuse ceiling ventilation systems. Diffuse ceiling systems are recent air distribution systems that supply cold air to the occupant area using perforated diffuse panels. These systems distribute air with a low velocity, minimizing the draft risk and dissatisfaction in highly dense spaces. The transmission risk of airborne infectious diseases like Covid-19 from the infected patient is high in waiting rooms. Thus, there is a demand to assure a secure environment for medical staff and patients in the waiting rooms. This study aims to numerically investigate the impact of the relative distance of the contamination source and exhaust on the transmission of airborne infectious diseases in the waiting room equipped with the diffuse ceiling ventilation system. In this regard, the release of Covid-19 from 4 different patients was investigated separately using the computational fluid dynamics technique. The distribution of the airborne infectious diseases is simulated by releasing SF6 tracer gas. The simulation result revealed that the contaminated patient located adjacent to the room’s outlet had no contamination risk for other patients and staff in the waiting room.

Place, publisher, year, edition, pages
International Society of Indoor Air Quality and Climate, 2022
Keywords
Diffuse ceiling ventilation system, Indoor air quality, Computational fluid dynamics, Tracer gas, Covid-19
National Category
Other Civil Engineering
Research subject
Civil and Architectural Engineering, Fluid and Climate Theory
Identifiers
urn:nbn:se:kth:diva-311614 (URN)2-s2.0-85159204362 (Scopus ID)
Conference
Indoor Air 2022 the 17th International Conference on Indoor Air Quality and Climate, June 12th to 16th Kuopio, Finland
Funder
Swedish National Infrastructure for Computing (SNIC), 2018-05973
Note

QC 20220629

Available from: 2022-05-01 Created: 2022-05-01 Last updated: 2023-08-14Bibliographically approved
Sadeghian, P. (2022). Computational fluid dynamics application in indoor air quality and health. (Doctoral dissertation). Stockholm: KTH Royal Institute of Technology
Open this publication in new window or tab >>Computational fluid dynamics application in indoor air quality and health
2022 (English)Doctoral thesis, comprehensive summary (Other academic)
Abstract [en]

Indoor air quality directly affects the comfort, performance, and well-being of occupants. Indoor pollution can cause immediate or long-term health effects and has been responsible for 4.1% of global deaths in recent decades. In operating rooms, providing a high indoor air quality is especially critical as surgical site infection can occur in patients due to air contamination in operating rooms.

Surgical site infections due to antibiotic resistant bacteria may threaten the safety and lives of millions of people each year. To moderate and reduce indoor contamination, it is necessary to select a proper ventilation strategy.Improving ventilation system performance requires a deep understanding of airflow patterns and contamination distribution.

This thesis adopted computational fluid dynamics to evaluate airflow patterns and the spread of airborne contaminations in indoor environments. Moreover, we sought to provide an approach to facilitate transferring the obtained knowledge to medical experts and decisionmakers to reduce the infection risk after the surgery.

The use of warming blankets has raised the concern about surgical site infections. Warming blankets are used to prevent hypothermia in patients during surgery. However, our results showed that these warming blankets reduce the bacteria-carrying particles level at the wound due to warm upward airflows.

Surgical lamps can block the airflow and generate a low-velocity area under the lamp that increases the accumulation of contaminants. The simulation results revealed that a novel fan-mounted surgical lamp reduced the contamination level to an acceptable range for infection-prone surgeries. This novel surgical lamp successfully reduced contamination in the operating room supplied with both turbulent mixing and laminar airflow ventilations.

In another study, we implemented a protective curtain and showed that this strategy could significantly reduce the exposure level of the medical team to a patient with infectious respiratory disease. This novel protective curtain is located between the patient’s upper body and the lower part during surgery. We found a 57% reduction in bacteria-carrying particle concentration at the wound by adopting this curtain. Thus, using this protective curtain can reduce the exposure level of both patient and surgical team in the operating room.

Besides investigating the performance of ventilation systems in hospitals, we investigated the application of diffuse ceilings ventilations in clinics, especially waiting rooms. Diffuse ceiling ventilation systems are common air distribution systems in offices and schools. Based on simulation results, a diffuse ceiling with a central opening and evenly distributed heat loads resulted in the highest cooling capacity and thermal comfort in clinic waiting rooms.

We have visualised the airflow field and airborne particles in operating rooms with the help of virtual reality techniques. We found the virtual reality environment more engaging to understand the airflow field and particle movements in operating rooms.

Abstract [sv]

Luftkvaliteten inomhus påverkar människors komfort, ochprestationsförmåga. Luftföroreningar inomhus kan orsaka omedelbaraoch långvariga hälsoeffekter och har orsakat 4,1 % av de globala dödsfallenunder de senaste decennierna. I operationssalar på sjukhus är det viktigtatt tillhandahålla god luftkvalitet. Infektioner i samband med operationkan drabba patienter på grund av förorenad luft i operationssalen.

Förekomst av infektioner i samband med kirurgiska ingrepp, och tillföljd av antibiotikaresistenta bakterier kan hota patientsäkerheten förmiljontals personer varje år. För att kontrollera och minska föroreningarinomhus är det nödvändigt att välja en korrekt ventilationsstrategi. För attförbättra ventilationssystemets prestanda krävs förståelse av hurventilationsluften strömmar och hur föroreningar sprider sig i rum.

I denna avhandling används numerisk strömningsmekanik ochexperimentella data för att utvärdera luftflödesmönster och spridning avluftburna föroreningar i inomhusmiljöer. Dessutom avser detta arbete atttillhandahålla ett tillvägagångssätt för att underlätta kunskapsöverföringtill medicinska experter och beslutsfattare för att minska infektionsriskenefter operationer.

Det finns oro för att patienter ska drabbas av postoperativasårinfektioner på grund av användning av medicintekniska produkter ioperationssalar, såsom värmande filtar. Värmefiltar används för attförhindra hypotermi hos patienter. Våra resultat visade dock attvärmefiltar minskar nivån av bakteriebärande partiklar vid såret på grundav uppåtgående varma luftflöden.

Operationslampor blockerar luftflödet och genererar ett område medlåg lufthastighet som ökar risken för ansamling av kontaminanter.Simuleringsresultaten visade att en ny fläktmonterad operationslampaminskade kontamineringsnivån till acceptabel nivå för infektionskänslig kirurgi. Den nya fläkten minskade kontaminationen i operationssalen vidsåväl turbulent som vid laminärt luftflöde.

I en annan studie implementerade vi en skyddande gardin som visadeatt den avsevärt minskade exponeringsnivån för det kirurgiska teametunder operation av en patient med infektion i luftvägarna. Dessutomrapporterades en 57 % minskning av den bakteriebärandepartikelkoncentrationen vid såret då gardinen användes. Skyddsgardinenförbättrar således säkerheten både för patienten och för operationsteamet.

Vi undersökte användning av diffunderande takventilation på kliniker.Diffunderande takventilation är vanligt förekommandeluftdistributionssystem i kontor och skolor. Baserat på simuleringar, gavinnertak med diffunderande tilluft ur central öppning, vid jämnt fördeladevärmelaster, den högsta kylkapaciteten och termiska komforten iklinikernas väntrum.

För visualisering av numeriska simuleringar användes teknik förvirtuell verklighet. Den virtuella verklighetsmiljön gav ökad upplevelse ochförståelse av luftflödesfältet och partikelrörelserna i operationssalar.

Place, publisher, year, edition, pages
Stockholm: KTH Royal Institute of Technology, 2022. p. 66
Series
TRITA-ABE-DLT ; 2211
Keywords
Ventilation systems, Indoor air quality (IAQ), Bacteria-carrying particles (BCP), Infectious respiratory disease, Operating room (OR), Thermal comfort, Computational fluid dynamics (CFD), ventilationssystem, bakteriebärande partiklar, infektionssjukdomar i luftvägarna, operationsrum, termisk komfort, numerisk strömningsmekanik
National Category
Other Civil Engineering
Research subject
Civil and Architectural Engineering, Fluid and Climate Theory
Identifiers
urn:nbn:se:kth:diva-311616 (URN)978-91-8040-188-3 (ISBN)
Public defence
2022-05-30, Kollegiesalen, Brinellvägen 8, KTH Campus, Videolänk: https://kth-se.zoom.us/meeting/register/u50tcuqoqzMiHd3HTd5gSLH46ifFK7UG_Gu5, Stockholm, 13:00 (English)
Opponent
Supervisors
Funder
Swedish Research Council Formas, 2017-01088Swedish National Infrastructure for Computing (SNIC), 2018-05973
Note

QC 20220502

Available from: 2022-05-02 Created: 2022-05-01 Last updated: 2022-06-25Bibliographically approved
Sadeghian, P. & Sadrizadeh, S. (2022). Impact of design parameters of diffuse ceiling ventilation systems on indoor air quality in school classrooms: a numerical assessment. In: : . Paper presented at BuildSim Nordic 2022:10th BuildSim Nordic conference and the 2nd International Nordic conference for IBPSA, 22nd-23rd August 2022, Copenhagen, Denmark. EDP Sciences
Open this publication in new window or tab >>Impact of design parameters of diffuse ceiling ventilation systems on indoor air quality in school classrooms: a numerical assessment
2022 (English)Conference paper, Published paper (Refereed)
Abstract [en]

Indoor air quality directly impacts an individual’s productivity and health condition in office buildings, hospitals, schools, and residential buildings. Diffuse ceiling systems have been used widely in classrooms at schools that have high heat loads. In this regard, this study investigated the role of diffuse ceiling design parameters, including active diffuse panels’ configuration and contamination locations, on indoor air quality in a classroom. The spread of airborne infectious diseases was simulated using computational fluid dynamics techniques. The results revealed that the central configuration of diffuse ceiling panels had the minimum spread of contaminations in the classroom compared to the dispersed configuration.

Place, publisher, year, edition, pages
EDP Sciences, 2022
Keywords
Diffuse ceiling ventilation system, Computational fluid dynamics, Airborne infectious diseases, Indoor air quality
National Category
Other Civil Engineering
Research subject
Civil and Architectural Engineering, Fluid and Climate Theory
Identifiers
urn:nbn:se:kth:diva-311615 (URN)10.1051/e3sconf/202236214001 (DOI)001299195500060 ()2-s2.0-85146859535 (Scopus ID)
Conference
BuildSim Nordic 2022:10th BuildSim Nordic conference and the 2nd International Nordic conference for IBPSA, 22nd-23rd August 2022, Copenhagen, Denmark
Funder
Swedish National Infrastructure for Computing (SNIC), 2018-05973Swedish Research Council Formas, 2017-01088
Note

QC 20220823

Available from: 2022-05-01 Created: 2022-05-01 Last updated: 2025-12-05Bibliographically approved
Sadrizadeh, S., Yao, R., Yuan, F., Awbi, H., Bahnfleth, W., Bi, Y., . . . Li, B. (2022). Indoor air quality and health in schools: A critical review for developing the roadmap for the future school environment. Journal of Building Engineering, 57, Article ID 104908.
Open this publication in new window or tab >>Indoor air quality and health in schools: A critical review for developing the roadmap for the future school environment
Show others...
2022 (English)In: Journal of Building Engineering, E-ISSN 2352-7102, Vol. 57, article id 104908Article in journal (Refereed) Published
Abstract [en]

Several research studies have ranked indoor pollution among the top environmental risks to public health in recent years. Good indoor air quality is an essential component of a healthy indoor environment and significantly affects human health and well-being. Poor air quality in such environments may cause respiratory disease for millions of pupils around the globe and, in the current pandemic-dominated era, require ever more urgent actions to tackle the burden of its impacts. The poor indoor quality in such environments could result from poor management, operation, maintenance, and cleaning. Pupils are a different segment of the population from adults in many ways, and they are more exposed to the poor indoor environment: They breathe in more air per unit weight and are more sensitive to heat/cold and moisture. Thus, their vulnerability is higher than adults, and poor conditions may affect proper development. However, a healthy learning environment can reduce the absence rate, improves test scores, and enhances pupil/teacher learning/teaching productivity. In this article, we analyzed recent literature on indoor air quality and health in schools, with the primary focus on ventilation, thermal comfort, productivity, and exposure risk. This study conducts a comprehensive review to summarizes the existing knowledge to highlight the latest research and solutions and proposes a roadmap for the future school environment. In conclusion, we summarize the critical limitations of the existing studies, reveal insights for future research directions, and propose a roadmap for further improvements in school air quality. More parameters and specific data should be obtained from in-site measurements to get a more in-depth understanding at contaminant characteristics. Meanwhile, site-specific strategies for different school locations, such as proximity to transportation routes and industrial areas, should be developed to suit the characteristics of schools in different regions. The socio-economic consequences of health and performance effects on children in classrooms should be considered. There is a great need for more comprehensive studies with larger sample sizes to study on environmental health exposure, student performance, and indoor satisfaction. More complex mitigation measures should be evaluated by considering energy efficiency, IAQ and health effects. 

Place, publisher, year, edition, pages
Elsevier BV, 2022
Keywords
Classroom air quality, Energy use in schools, Exposure risk, Particle matter, Ventilation, Volatile organic compounds
National Category
Other Civil Engineering
Research subject
Civil and Architectural Engineering, Fluid and Climate Theory
Identifiers
urn:nbn:se:kth:diva-315583 (URN)10.1016/j.jobe.2022.104908 (DOI)000855584200002 ()2-s2.0-85135389777 (Scopus ID)
Funder
Swedish Research Council Formas, 2021-01422
Note

QC 20221005

Available from: 2022-07-08 Created: 2022-07-08 Last updated: 2022-10-05Bibliographically approved
Sadeghian, P., Bi, Y., Cao, G. & Sadrizadeh, S. (2022). Reducing the risk of viral contamination during the coronavirus pandemic by using a protective curtain in the operating room. Patient Safety in Surgery, 16(1)
Open this publication in new window or tab >>Reducing the risk of viral contamination during the coronavirus pandemic by using a protective curtain in the operating room
2022 (English)In: Patient Safety in Surgery, E-ISSN 1754-9493, Vol. 16, no 1Article in journal (Refereed) Published
Abstract [en]

Background: Airborne transmission diseases can transfer long and short distances via sneezing, coughing, and breathing. These airborne repertory particles can convert to aerosol particles and travel with airflow. During the Coronavirus disease 2019 (COVID-19) pandemic, many surgeries have been delayed, increasing the demand for establishing a clean environment for both patient and surgical team in the operating room.

Methods: This study aims to investigate the hypothesis of implementing a protective curtain to reduce the transmission of infectious contamination in the surgical microenvironment of an operating room. In this regard, the spread of an airborne transmission disease from the patient was evaluated, consequently, the exposure level of the surgical team. In the first part of this study, a mock surgical experiment was established in the operating room of an academic medical center in Norway. In the second part, the computational fluid dynamic technique was performed to investigate the spread of airborne infectious diseases. Furthermore, the field measurement was used to validate the numerical model and guarantee the accuracy of the applied numerical models.

Results: The results showed that the airborne infectious agents reached the breathing zone of the surgeons. However, using a protective curtain to separate the microenvironment between the head and lower body of the patient resulted in a 75% reduction in the spread of the virus to the breathing zone of the surgeons. The experimental results showed a surface temperature of 40 ˚C, which was about a 20 ˚C increase in temperature, at the wound area using a high intensity of the LED surgical lamps. Consequently, this temperature increase can raise the patient's thermal injury risk.

Conclusion: The novel method of using a protective curtain can increase the safety of the surgical team during the surgery with a COVID-19 patient in the operating room.

Place, publisher, year, edition, pages
Springer Nature, 2022
National Category
Other Civil Engineering
Research subject
Civil and Architectural Engineering, Fluid and Climate Theory
Identifiers
urn:nbn:se:kth:diva-311612 (URN)10.1186/s13037-022-00332-x (DOI)000836781800001 ()35933393 (PubMedID)2-s2.0-85135582680 (Scopus ID)
Funder
Swedish Research Council Formas, 2017-01088Swedish National Infrastructure for Computing (SNIC), 2018-05973
Note

QC 20220912

Available from: 2022-05-01 Created: 2022-05-01 Last updated: 2023-12-15Bibliographically approved
Sadeghian, P., Rahnama, S., Afshari, A. & Sadrizadeh, S. (2022). The role of design parameters on the performance of diffuse ceiling ventilation systems – thermal comfort analyses for indoor environment. Advances in Building Energy Research, 1-19
Open this publication in new window or tab >>The role of design parameters on the performance of diffuse ceiling ventilation systems – thermal comfort analyses for indoor environment
2022 (English)In: Advances in Building Energy Research, ISSN 1751-2549, E-ISSN 1756-2201, p. 1-19Article in journal (Refereed) Published
Abstract [en]

Thermal comfort conditions profoundly affect the occupants’ health and productivity. A diffuse ceiling ventilation system is an air distribution system in which the air is supplied to the occupied zone with relatively a low velocity through the perforated panels installed in the ceiling. The current study evaluated the impact of diffuse ceiling design parameters, i.e. diffuse panel configurations and heat load distributions, on the thermal comfort condition of the occupants. In this regard, the computational fluid dynamics technique was used to evaluate thermal comfort conditions in a waiting room, meeting room and office. The central and dispersal configuration of active diffuse panels was considered. The PMV-PPD model was applied to evaluate the overall occupants’ comfort, while the draft rate was considered to assess local thermal comfort. The model validation was performed by comparing the collected laboratory measurement data. Overall, the results indicated that the central active diffuse panel configuration had a better thermal comfort than the dispersed one. The evaluation of dispersed configuration in realist scenarios, including office and waiting room, had the highest dissatisfaction, with a PPD value of 9%. Local thermal comfort assessment revealed that dispersed configuration had the highest draft rate of 14% in the office.

Place, publisher, year, edition, pages
Informa UK Limited, 2022
Keywords
Diffuse ceiling ventilation, thermal comfort, PMV-PPD model, draft rate, computational fluid dynamics simulation
National Category
Other Civil Engineering
Research subject
Civil and Architectural Engineering, Fluid and Climate Theory
Identifiers
urn:nbn:se:kth:diva-311613 (URN)10.1080/17512549.2022.2109211 (DOI)000840368800001 ()2-s2.0-85135948096 (Scopus ID)
Funder
Swedish National Infrastructure for Computing (SNIC), 2018-05973Swedish Research Council Formas, 2017-01088
Note

QC 20220817

Available from: 2022-05-01 Created: 2022-05-01 Last updated: 2026-01-30Bibliographically approved
Sadeghian, P., Höjerback, P. & Sadrizadeh, S. (2021). Does a fixed temperature-controlled airflow ventilation system reduce airborne infectious disease in clinics? A numerical investigation. In: : . Paper presented at Healthy Buildings 2021, Hawaii, USA.
Open this publication in new window or tab >>Does a fixed temperature-controlled airflow ventilation system reduce airborne infectious disease in clinics? A numerical investigation
2021 (English)Conference paper, Oral presentation with published abstract (Refereed)
Abstract [en]

HVAC systems play an important role in moderating and controlling both surgical site infections and airborne infectious disease transmission in hospitals and clinics. Designing a proper HVAC system can minimize the airborne particles' concentration and prevent the spread of contaminated agents to the wound area, instruments and implants, and the medical team. Various ventilation system strategies have been developed to reduce the airborne particles in the air during the surgeries. The turbulent mixing, laminar airflow, and temperature-controlled airflowventilations are three common operating room ventilation systems used in rooms where major surgeries are conducted. However, mobile ventilation systems are mostly applied for minor surgeries and dental treatments that mainly supply a mixing airflow with random directions.Several studies revealed that instead using a mobile laminar airflow ventilation system successfully reduced the contamination level; however, the washing effect of such systems is limited to distance and location. In this regard, this research investigates the impact of using a novel fixed ventilation system based on the principle of temperature-controlled airflow on the reduction of both the SSI and cross-contamination risks in patients and medical teams during minor surgeries. The airflow behavior and airborne particle distribution are simulated by using computational fluid dynamics (CFD) techniques.

Keywords
Ventilation systems, Airborne particles, Minor surgery
National Category
Other Civil Engineering
Research subject
Civil and Architectural Engineering, Fluid and Climate Theory
Identifiers
urn:nbn:se:kth:diva-300102 (URN)
Conference
Healthy Buildings 2021, Hawaii, USA
Note

QC 20211110

Available from: 2021-08-24 Created: 2021-08-24 Last updated: 2022-06-25Bibliographically approved
Sadeghian, P., Duwig, C., Sköldenberg, O., Tammelin, A., Rahimi Hosseini, A. & Sadrizadeh, S. (2021). Numerical investigation of the impact of warming blankets on the performance of ventilation systems in the operating room. Advances in Building Energy Research, 1-23
Open this publication in new window or tab >>Numerical investigation of the impact of warming blankets on the performance of ventilation systems in the operating room
Show others...
2021 (English)In: Advances in Building Energy Research, ISSN 1751-2549, E-ISSN 1756-2201, p. 1-23Article in journal (Refereed) Published
Abstract [en]

Patient warming is an efficient approach to preventing hypothermia during surgeries. Hypothermia increases the risk of postoperative infections, bleeding, transfusion demand, prolonging postoperative recovery, drug metabolism duration and vasoconstriction. Although the use of warming blankets addresses the problem of a decrease in a patient’s core body temperature, concern remains that the heat emitted by these warming blankets can disturb the supplied clean air by the ventilation system and thus increase the contamination level of airborne particles.

The main purpose of this study is to numerically investigate the impact of using warming blankets on the performance of two common ventilation systems – unidirectional flow and mixing ventilation – in an operating room. The effect of using forced-air and conductive warming blankets on the distribution of bacteria-carrying particles and airflow behaviour were simulated in the operating room. The results showed that applying the forced-air warming blanket considerably increased the average air temperature at the wound area and under the surgical drape. Thus, the forced-air warming blanket can be more effective than the conductive blankets in warming the patient during the surgery. However, using the contaminated forced-air warming blanket resulted in a considerable increase in the contamination concentration at the wound surface.

Keywords
Airborne particles, Hypothermia, Unidirectional flow ventilation, Mixing ventilation, Computational fluid dynamics
National Category
Other Civil Engineering
Research subject
Civil and Architectural Engineering, Fluid and Climate Theory
Identifiers
urn:nbn:se:kth:diva-284538 (URN)10.1080/17512549.2021.2009911 (DOI)000731211300001 ()2-s2.0-85121706457 (Scopus ID)
Funder
Swedish Research Council Formas, 2017- 01088Swedish National Infrastructure for Computing (SNIC), 2018-05973
Note

QC 20220607

Available from: 2020-10-28 Created: 2020-10-28 Last updated: 2026-01-30Bibliographically approved
Organisations
Identifiers
ORCID iD: ORCID iD iconorcid.org/0000-0001-7032-3049

Search in DiVA

Show all publications