SISO Transfer Functions for Stability Analysis of Grid-Connected Voltage-Source Converters
ABB, Västerås, Sweden.ORCID iD: 0000-0002-3107-7073
Show others and affiliations
2019 (English)In: IEEE transactions on industry applications, ISSN 0093-9994, E-ISSN 1939-9367, Vol. 55, no 3, p. 2931-2941, article id 8640057Article in journal (Refereed) Published
Abstract [en]

Converter-grid interaction is of great interest in a weak-grid condition. This paper presents a single-input-single-output (SISO) open-loop transfer function for the stability analysis of grid-connected voltage-source converters. Differing from the conventional input impedance method and the eigenvalue analysis, an alternative multi-input-multi-output closed-loop system is developed in the paper and it eventually yields an SISO open-loop transfer function. This enables the application of a single Nyquist curve for analyzing the overall system stability. The model is validated against time-domain simulations as well as experimental results showing excellent accuracy for predicting the system stability.

Place, publisher, year, edition, pages
Institute of Electrical and Electronics Engineers Inc. , 2019. Vol. 55, no 3, p. 2931-2941, article id 8640057
Keywords [en]
Multi-input-multi-output (MIMO), Nyquist stability criterion, single-input-single-output (SISO), voltage-source converter (VSC), weak grid, Closed loop systems, Eigenvalues and eigenfunctions, MIMO systems, Stability criteria, System stability, Telecommunication repeaters, Time domain analysis, Multi input multi output, Single input single output, Voltage source converters, Transfer functions
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
URN: urn:nbn:se:kth:diva-252523DOI: 10.1109/TIA.2019.2898978ISI: 000466033700073Scopus ID: 2-s2.0-85064988163OAI: oai:DiVA.org:kth-252523DiVA, id: diva2:1324293
Note

QC 20190613

Available from: 2019-06-13 Created: 2019-06-13 Last updated: 2022-06-26Bibliographically approved
In thesis
1. On Modeling and Stability Analysis of Grid-Connected Voltage Source Converters
Open this publication in new window or tab >>On Modeling and Stability Analysis of Grid-Connected Voltage Source Converters
2021 (English)Doctoral thesis, comprehensive summary (Other academic)
Abstract [en]

With increasing deployment of voltage source converters (VSCs) in the grid, instability phenomena due to converter--grid interactions have been observed. Modeling and stability analysis of grid-connected VSCs have become popular research topics. Moreover, the power system is losing its inertia with increased penetration of renewable energy resources. Large and fast frequency deviations tend to vary more frequently compared to the conventional grid. The control and modeling of VSCs in the low-inertia grid is thus a crucial topic. The main objective of this thesis is the small-signal modeling and stability analysis of grid-connected VSCs. 

As a result of the asymmetrical synchronous reference ($ dq $) frame dynamics, the structure of the dynamical system is multi-input multi-output (MIMO). Conventionally, the small-signal stability analysis for such a system is conducted either by the modal-analysis approach or the impedance based method, which is based on MIMO. In this thesis, methods for modeling and analyzing a MIMO system using a single-input single-output (SISO) approach are developed. Compared to conventional methods, the SISO methods overcome the difficulties of defining the stability margins for individual closed loops. Moreover, the methods provide intuitive solutions to the design of controllers for individual closed loops. 

The thesis also investigates the control and modeling of grid-connected VSCs connected to low-inertia grids. It is illustrated that, for improvement of network frequency dynamics, a VSC with proper energy storage is capable to emulate inertial response from a synchronous machine. Moreover, other frequency control strategies are shown to be beneficial, compared to the inertial emulation. In addition, the inaccuracies for the $ dq $-frame small-signal model, in the presence of phase jumps and frequency deviations, are investigated. It is concluded that the inaccuracy of the small-signal model always exists under phase jumps. In the presence of frequency deviation, the stability analysis shall be evaluated at the steady-state operating point of the frequency.

Abstract [sv]

Med ökad användning av spänningsstyva omriktare (VSC) i nätet har instabilitetsfenomen på grund av växelverkan mellan omriktare och nät observerats. Modellering och analys av stabiliteten hos nätanslutna omriktare har därför utvecklats till ett populärt och omfattande forskningsämne. Ökad andel förnybara energikällor har dessutom inneburit att elkraftsystemet har förlorat delar av sina tröghetsmassor. Det leder till att stora och snabba frekvensavvikelser är vanligare i jämförelse med förhållandena i konventionella nät. Modellering och reglering av spänningsstyva omriktare i nät med låg tröghet är således av avgörande betydelse. Huvudsyftet med avhandling har varit att utveckla småsignalmodeller för nätanslutna omriktare och analysera stabiliteten hos dessa.

Som ett resultat av dynamiken hos det synkrona koordinatsystemet ($dq$) är strukturen för det dynamiska systemet s.k. multiple-input multiple-output (MIMO). Konventionellt analyseras, för ett sådant system, småsignalstabiliteten antingen genom modalanalys eller genom en impedansmetod baserad på MIMO. En av målsättningarna i avhandlingen har varit att utveckla metoder, för modellering och analys av ett MIMO-system, baserat på en single-input single-output (SISO) formulering av systemet. I jämförelse med de konventionella metoderna löser SISO-metoderna svårigheterna med att definiera stabilitetsmarginalerna för enskilda slutna slingor. Metoderna ger dessutom intuitiva lösningar för utformningen av regleringen av enskilda slingor. 

Avhandlingen undersöker också modellering och reglering av nätanslutna VSC:er anslutna till nät med liten tröghet. I avhandlingen illustreras hur en VSC med korrekt energilagring är kapabel att emulera tröghetsresponsen från en synkronmaskin i avseende att förbättra nätets frekvensdynamik. Även andra strategier för frekvenskontroll har visat sig vara fördelaktiga. Avslutningsvis undersöks de fel som introduceras i småsignalmodellen i samband med fas- och frekvensändringar. Slutsatsen är att småsignalmodellens fel alltid existerar under fasförändringar. Vid frekvensavvikelser ska stabilitetsanalysen ske vid den aktuella frekvensen i det stationära fallet.

Place, publisher, year, edition, pages
KTH Royal Institute of Technology, 2021
Series
TRITA-EECS-AVL ; 2021:28
Keywords
Low-inertia grid, multiple-input multiple-output (MIMO), single-input single-output (SISO), small-signal model, stability analysis, voltage source converters (VSCs)
National Category
Other Electrical Engineering, Electronic Engineering, Information Engineering
Research subject
Electrical Engineering
Identifiers
urn:nbn:se:kth:diva-294393 (URN)978-91-7873-856-4 (ISBN)
Public defence
2021-06-04, Ångdomen, Osquars backe 31, Kungliga Tekniska högskolan, Brinellvägen 8, Stockholm, 10:00 (English)
Opponent
Supervisors
Note

QC 20210518

Available from: 2021-05-18 Created: 2021-05-17 Last updated: 2022-09-16Bibliographically approved

Open Access in DiVA

No full text in DiVA

Other links

Publisher's full textScopus

Authority records

Harnefors, LennartNee, Hans-Peter

Search in DiVA

By author/editor
Harnefors, LennartNee, Hans-Peter
By organisation
Electric Power and Energy Systems
In the same journal
IEEE transactions on industry applications
Electrical Engineering, Electronic Engineering, Information Engineering

Search outside of DiVA

GoogleGoogle Scholar

doi
urn-nbn

Altmetric score

doi
urn-nbn
Total: 655 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf