In this study, we investigate the influence of the pressure and temperature drops in the suction and return lines on the energy consumption of a supermarket refrigeration plant. We calculate the energy consumption of CO2indirect systems with R404A, ammonia or propane as the primary refrigerant and compare it to conventional direct expansion (DX) system with R404A or R502. CO2pressure drop and the corresponding saturation temperature drop in the indirect circuit is calculated and compared to that of R404A. The energy consumption of R404A/CO2indirect systems was found to be very close to R404A-DX system using the same pipe size in the return and suction lines. Replacing R404A by ammonia or propane in the indirect system reduced the energy consumption. This study indicates that it is more economical to use CO2indirect system with proper primary refrigerant rather than using the conventional DX systems.