Experimental study of the pressure reset control strategy for energy-efficient fan operation: Part 1: Variable air volume ventilation system with dampers
KTH, Skolan för arkitektur och samhällsbyggnad (ABE), Byggvetenskap, Strömnings- och klimatteknik. Aalborg University, Denmark.ORCID-id: 0000-0002-9361-1796
2017 (engelsk)Inngår i: Energy and Buildings, ISSN 0378-7788, E-ISSN 1872-6178, Vol. 139, s. 72-77Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]

This paper is the first part of a two-part series which investigate the energy saving potentials in a novel mechanical ventilation system by replacing terminal dampers with decentralized fans. In Part 1, a conventional variable air volume (VAV) ventilation system with dampers is studied as a reference for comparison with the novel ventilation system in Part 2. The present study (Part 1) proposes a new method to implement the pressure reset strategy in practice. A common strategy to control the supply fan speed in a VAV system is to install a pressure sensor in the supply duct system. Then the fan speed is controlled such that a constant static pressure is maintained at the sensor location. Further energy saving can be obtained by resetting the pressure setpoint to a lower value at partial load conditions. This strategy is known as pressure reset control or critical zone reset strategy in the literature. The proposed method has been evaluated through an experimental mock-up in a laboratory environment. Experimental results show a minimum reduction of about 20% in fan power demand with applying the reset strategy compared to a constant static pressure setpoint.

sted, utgiver, år, opplag, sider
Elsevier, 2017. Vol. 139, s. 72-77
Emneord [en]
Critical zone reset, Energy efficient control, Pressure reset, VAV ventilation system
HSV kategori
Identifikatorer
URN: urn:nbn:se:kth:diva-200868DOI: 10.1016/j.enbuild.2016.12.080ISI: 000395599200008Scopus ID: 2-s2.0-85008870028OAI: oai:DiVA.org:kth-200868DiVA, id: diva2:1072070
Merknad

QC 20170207

Tilgjengelig fra: 2017-02-07 Laget: 2017-02-03 Sist oppdatert: 2024-03-18bibliografisk kontrollert

Open Access i DiVA

Fulltekst mangler i DiVA

Andre lenker

Forlagets fulltekstScopus

Person

Sadrizadeh, Sasan

Søk i DiVA

Av forfatter/redaktør
Sadrizadeh, Sasan
Av organisasjonen
I samme tidsskrift
Energy and Buildings

Søk utenfor DiVA

GoogleGoogle Scholar

doi
urn-nbn

Altmetric

doi
urn-nbn
Totalt: 222 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf