Endre søk
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf
Control of Dynamically Assisted Phase-shifting Transformers
KTH, Skolan för elektro- och systemteknik (EES), Elektriska maskiner och effektelektronik.
2008 (engelsk)Licentiatavhandling, med artikler (Annet vitenskapelig)
Abstract [en]

In this thesis, controllers for power oscillation damping, transient stability improvement and power flow control by means of a Controlled Series Compensator (CSC) and and a Dynamic Power Flow Controller (DPFC) are proposed. These devices belong to the group of power system components referred to as Flexible AC Transmission System (FACTS) devices. The developed controllers use only quantities measured locally at the FACTS device as inputs, thereby avoiding the risk of interrupted communications associated with the use of remote signals for control.

For power systems with one dominating, poorly damped inter-area power oscillation mode, it is shown that a simple generic system model can be used as a basis for damping- and power flow control design. The model for control of CSC includes two synchronous machine models representing the two grid areas participating in the oscillation and three reactance variables, representing the interconnecting transmission lines and the FACTS device. The model for control of DPFC is of the same type but it also includes the phase shift of the internal phase-shifting transformer of the DPFC.

The key parameters of the generic grid models are adaptively set during the controller operation by estimation from the step responses in the FACTS line power to the changes in the line series reactance inserted by the FACTS device. The power oscillation damping controller is based on a time-discrete, non-linear approach which aims to damp the power oscillations and set the desired power flow on the FACTS line by means of two step changes in the line reactance separated in time by half an oscillation cycle.

A verification of the proposed controllers was done by means of digital simulations using power system models of different complexities. The CSC and DPFC controllers were shown to significantly improve the small-signal- and transient stability in one four-machine system of a type commonly used to study inter-area oscillations. The CSC controller was also tested for 18 different contingencies in a 23-machine system, resulting in an improvement in both the system transient stability and the damping of the critical oscillation mode.

sted, utgiver, år, opplag, sider
Stockholm: KTH , 2008. , s. x, 172
Serie
Trita-EE, ISSN 1653-5146 ; 2008:008
Emneord [en]
Thyristor Controlled Series Capacitor, Thyristor Switched Series Capacitor, Controlled Series Compensator, Dynamic Power Flow Controller, Phase-Shifting Transformer, Power Oscillation Damping, Transient Stability, Power Flow Control, Adaptive Control
HSV kategori
Identifikatorer
URN: urn:nbn:se:kth:diva-4653ISBN: 978-91-7178-879-5 (tryckt)OAI: oai:DiVA.org:kth-4653DiVA, id: diva2:13258
Presentation
2008-03-28, E2, Lindstedtsvägen 3, KTH, 13:00
Opponent
Veileder
Merknad
QC 20101112Tilgjengelig fra: 2008-02-27 Laget: 2008-02-27 Sist oppdatert: 2022-06-26bibliografisk kontrollert
Delarbeid
1. Estimation of grid parameters for the control of variable series reactance FACTS devices
Åpne denne publikasjonen i ny fane eller vindu >>Estimation of grid parameters for the control of variable series reactance FACTS devices
2006 (engelsk)Inngår i: 2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, s. 105-111Konferansepaper, Publicerat paper (Fagfellevurdert)
Abstract [en]

For high performance control of Flexible AC Transmission System (FACTS) devices with controllable reactances, a representation of the surrounding grid is essential. Using such a model, an adaptive control strategy can be developed which optimizes the control in real time as the grid parameters change. This paper proposes such a generic grid model and derives the theory of how to estimate the main parameters using measurements of the line active power response from small step reactance changes. The estimation methods are verified using simple grid models in PSCAD simulations and more advanced grid models using SIMPOW simulations of a modified version of the CIGRE Nordic 32 grid. This work should be thought of as a foundation for developing control systems for variable series reactance FACTS devices.

Serie
IEEE Power Engineering Society General Meeting, ISSN 1932-5517
Emneord
parameter estimation, power system stability, power transmission control, prediction methods, FACTS
HSV kategori
Identifikatorer
urn:nbn:se:kth:diva-8038 (URN)10.1109/PES.2006.1708919 (DOI)000247080000022 ()2-s2.0-35348928218 (Scopus ID)978-1-4244-0492-6 (ISBN)
Konferanse
General Meeting of the Power-Engineering-Society, Montreal, CANADA, JUN 18-22, 2006
Merknad
QC 20101112Tilgjengelig fra: 2008-02-27 Laget: 2008-02-27 Sist oppdatert: 2024-01-18bibliografisk kontrollert
2. Discrete open loop control for power oscillation damping utilizing variable series reactance FACTS devices
Åpne denne publikasjonen i ny fane eller vindu >>Discrete open loop control for power oscillation damping utilizing variable series reactance FACTS devices
2006 (engelsk)Inngår i: PROCEEDINGS OF THE 41ST INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, 2006, s. 785-789Konferansepaper, Publicerat paper (Fagfellevurdert)
Abstract [en]

This paper describes an open loop method of controlling FACTS devices for power oscillation damping. The method is based on step-wise series reactance modulation. The principle of the method is to stabilize an oscillation in a power system which is characterized by one major mode of oscillation by switching a reactance in series with one transmission line, thereby changing the total reactance between the areas participating in the oscillation. In order to stabilize the system during an oscillation, the stationary voltage angle difference between the areas is changed to coincide with the present angle at a point where the speed of the lumped machine representations of the areas is nominal. This is the case at the peaks of the oscillation. To determine the required size of the reactance step, a reduced model of the power system is used. The model parameters are continuously updated using local measurements of the active power on the reactance controlled line. Several approaches for damping with different numbers of steps are presented and verified using digital simulations of power system models.

Emneord
Damping, Electric impedance, Electric power systems, Electric power transmission networks, Model structures, Modulation, Active Power (CO), angle difference, Digital simulations, FACTS (Flexible AC Transmission System) devices, In order, International (CO), Local measurements, machine representations, Model parameters, Open loop controlling, Open-loop method, power engineering, Power oscillation damping, Power system modelling, power systems, Reduced models, Transmission line (TL)
HSV kategori
Identifikatorer
urn:nbn:se:kth:diva-8039 (URN)10.1109/UPEC.2006.367586 (DOI)000256054900159 ()2-s2.0-46849086754 (Scopus ID)
Konferanse
41st International Universities Power Engineering Conference, Newcastle upon Tyne, ENGLAND, SEP 06, 2006-SEP 08, 2008
Merknad
QC 20101112Tilgjengelig fra: 2008-02-27 Laget: 2008-02-27 Sist oppdatert: 2024-01-18bibliografisk kontrollert
3. An adaptive model predictive approach to power oscillation damping utilizing variable series reactance FACTS devices
Åpne denne publikasjonen i ny fane eller vindu >>An adaptive model predictive approach to power oscillation damping utilizing variable series reactance FACTS devices
2006 (engelsk)Inngår i: PROCEEDINGS OF THE 41ST INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, 2006, s. 790-794Konferansepaper, Publicerat paper (Fagfellevurdert)
Abstract [en]

This paper describes an adaptive method of controlling FACTS devices for power oscillation damping. The method is based on step-wise series reactance modulation. Here, a reduced model of the power system with only two rotating masses is used as a basis for the control design. The model parameters are updated using local measurements of the active power on the controlled line. An adaptive closed loop controller is developed based on the principle that it is possible to stabilize an oscillation in a power system which is characterized by one major mode of oscillation by switching a reactance in series with one transmission line in a small number of steps. The reduced model parameters are recomputed when new information of the system response is known making the control scheme an adaptive one. The paper also includes the derivation of a damping controller with a power flow control feature and a verification of the controllers using digital simulations of power system models of different complexities.

HSV kategori
Identifikatorer
urn:nbn:se:kth:diva-8040 (URN)10.1109/UPEC.2006.367587 (DOI)000256054900160 ()2-s2.0-46849089203 (Scopus ID)978-1-86135-342-9 (ISBN)
Konferanse
41st International Universities Power Engineering Conference, Newcastle upon Tyne, ENGLAND, SEP 06, 2006-SEP 08, 2008
Merknad
QC 20101112Tilgjengelig fra: 2008-02-27 Laget: 2008-02-27 Sist oppdatert: 2024-01-18bibliografisk kontrollert
4. Adaptive control of controlled series compensators for power system stability improvement
Åpne denne publikasjonen i ny fane eller vindu >>Adaptive control of controlled series compensators for power system stability improvement
2007 (engelsk)Inngår i: 2007 IEEE LAUSANNE POWERTECH, 2007, s. 355-360Konferansepaper, Publicerat paper (Fagfellevurdert)
Abstract [en]

This paper describes the design and verification of a time-discrete adaptive controller for damping of inter-area power oscillations, power flow control, and transient stability improvement Only locally measured signals are used as inputs to the controller. The controller may be used with any FACTS device which operates as a variable series reactance in the power grid, such as for example the TCSC. The controller is based on a reduced system model which relies on the assumption of one dominating inter-area oscillation mode in the power system where the FACTS device is placed. Verification of the controller is performed by means of digital simulations of a four-machine system commonly used to study inter-area oscillations.

Emneord
control, FACTS, power oscillation, TCSC, TSSC, transient stability
HSV kategori
Identifikatorer
urn:nbn:se:kth:diva-8041 (URN)10.1109/PCT.2007.4538343 (DOI)000258730100062 ()2-s2.0-50849087016 (Scopus ID)978-1-4244-2189-3 (ISBN)
Konferanse
IEEE Lausanne Powertech, Lausanne, SWITZERLAND, JUL 01-05, 2007
Merknad
QC 20101112Tilgjengelig fra: 2008-02-27 Laget: 2008-02-27 Sist oppdatert: 2024-01-18bibliografisk kontrollert
5. A dynamic power flow controller for power system stability improvement and loss reduction
Åpne denne publikasjonen i ny fane eller vindu >>A dynamic power flow controller for power system stability improvement and loss reduction
2008 (engelsk)Inngår i: The 16th Power Systems Computation Conference, Power Systems Computation Conference ( PSCC ) , 2008Konferansepaper, Publicerat paper (Fagfellevurdert)
Abstract [en]

In this paper, a novel FACTS device denoted Dynamic Power Flow Controller (DPFC) is described. The device consists of a Phase-Shifting Transformer (PST) connected in series with a set of thyristor-switched capacitive and/or inductive elements. When compared to a normal PST, this device has faster dynamic properties and in addition to the normal PST functions, it also allows for power oscillation damping, transient stability improvement, and voltage stability improvement in a power grid. The DPFC is believed to be less costly than other FACTS devices with the same functionalities. In this paper, the benefits and functions of the DPFC are discussed. Additionally, an adaptive controller for DPFC power oscillation damping, transient stability improvement, and power flow control is presented and verified by means of digital simulations.

sted, utgiver, år, opplag, sider
Power Systems Computation Conference ( PSCC ), 2008
Emneord
Adaptive control, Dynamic Power Flow Controller, FACTS, Phase-Shifting Transformer, Power Oscillation Damping, Transient Stability, Power Flow Control
HSV kategori
Identifikatorer
urn:nbn:se:kth:diva-8042 (URN)2-s2.0-84944111649 (Scopus ID)
Konferanse
16th PSCC, Glasgow, Scotland, July 14-18, 2008
Merknad

QC 20101112

Tilgjengelig fra: 2008-02-27 Laget: 2008-02-27 Sist oppdatert: 2024-01-18bibliografisk kontrollert

Open Access i DiVA

fulltekst(2357 kB)6458 nedlastinger
Filinformasjon
Fil FULLTEXT01.pdfFilstørrelse 2357 kBChecksum SHA-1
329565306bfa45685f093b6dfd1ee2c2213609b8ca075431ab6ca1ccd63fb1331f90fe59
Type fulltextMimetype application/pdf

Søk i DiVA

Av forfatter/redaktør
Johansson, Nicklas
Av organisasjonen

Søk utenfor DiVA

GoogleGoogle Scholar
Totalt: 6517 nedlastinger
Antall nedlastinger er summen av alle nedlastinger av alle fulltekster. Det kan for eksempel være tidligere versjoner som er ikke lenger tilgjengelige

isbn
urn-nbn

Altmetric

isbn
urn-nbn
Totalt: 1617 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf