Evaluation of Direct and Indirect Methods for Occupancy Detection and Air Quality Control in Buildings
KTH, Skolan för industriell teknik och management (ITM), Energiteknik.
2025 (engelsk)Independent thesis Advanced level (degree of Master (Two Years)), 20 poäng / 30 hpOppgave
Abstract [en]

This thesis investigates a range of sensor-based methodologies for the detection of occupancy in indoor environments, with the objective of improving HVAC control and energy efficiency. The research was conducted in the Bäckström Conference Room at KTH, utilizing existing environmental sensors, including CO₂, temperature, humidity, a PIR motion sensor, and custom-designed Bluetooth Low Energy tracking systems developed on ESP32 microcontrollers.

Among the techniques assessed, CO₂ concentration emerged as the most reliable single indicator of occupancy, demonstrating a robust correlation (R² = 0.98) with the actual headcount. While temperature and relative humidity provided useful insights into the dynamics and stratification of the indoor environment, their individual predictive capabilities were found to be limited. The PIR sensor predominantly functioned to verify presence due to its less precise measurement resolution. The BLE-based approaches comprised two distinct methodologies. The first was a BLE device counter that passively detects nearby broadcasting devices, showing a strong correlation with occupancy data. A linear regression model developed using the device count achieved an R² value of 0.874 with a dataset characterized by a limited number of occupants and devices. The second methodology focused on analyzing the BLE signal strength (RSSI) between a transmitter-receiver pair. Although this approach did not facilitate occupant counting, it enabled the detection of occupant positioning and movement patterns within the space by examining signal attenuation characteristics.

Occupancy data were employed to develop adaptive occupancy schedules, which were subsequently implemented in IDA ICE building simulations. The objective of these simulations was to evaluate the potential energy savings achievable through occupancy-based HVAC control by comparing dynamic, sensor-informed occupancy profiles with conventional static profiles grounded in EN 16798-1 standards. Importantly, this research focused on assessing two distinct occupancy scenarios within the same HVAC system configuration, rather than analyzing different energy control technologies. The results indicated a significant reduction in annual HVAC energy consumption when authentic occupancy data were utilized, highlighting the critical impact of internal gains on energy demand. The Bäckström Room, characterized as a thermally stable and controlled environment, relies predominantly on the Mechanical Supply Air system for temperature regulation, with minimal contributions from active heating and cooling systems.

sted, utgiver, år, opplag, sider
2025. , s. 86
Serie
TRITA-ITM-EX ; 2025:233
Emneord [en]
Air quality control, Occupancy detection, Smart buildings
HSV kategori
Identifikatorer
URN: urn:nbn:se:kth:diva-366146OAI: oai:DiVA.org:kth-366146DiVA, id: diva2:1981446
Fag / kurs
Energy Technology
Utdanningsprogram
Master of Science - Sustainable Energy Engineering
Veileder
Examiner
Tilgjengelig fra: 2025-07-04 Laget: 2025-07-04 Sist oppdatert: 2025-08-19

Open Access i DiVA

fulltext(1893 kB)89 nedlastinger
Filinformasjon
Fil FULLTEXT02.pdfFilstørrelse 1893 kBChecksum SHA-512
cbc79ceec72ecc5ec97e3d5e8252eb451b9cf54441499d3aaa3c0270ba86ed7bd9bc8dd1b60dadbeb3e6296bb875c82fa4798d264dbf09a1e4b02201fa5e5615
Type fulltextMimetype application/pdf

Av organisasjonen

Søk utenfor DiVA

GoogleGoogle Scholar
Totalt: 122 nedlastinger
Antall nedlastinger er summen av alle nedlastinger av alle fulltekster. Det kan for eksempel være tidligere versjoner som er ikke lenger tilgjengelige

urn-nbn

Altmetric

urn-nbn
Totalt: 386 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf