A Cascaded Hybrid Synchronization Control for Grid-Connected InvertersVise andre og tillknytning
2026 (engelsk)Inngår i: IEEE transactions on power electronics, ISSN 0885-8993, E-ISSN 1941-0107, Vol. 41, nr 1, s. 137-142Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]
This letter revisits vector voltage control (VVC) and finds that by introducing a P-E-q droop into the q-axis voltage reference, a conventional phase-locked loop (PLL) can effectively substitute the power synchronization control for replicating the power-frequency (angle) dynamics of grid-forming (GFM) inverters. Consequently, a simple GFM control strategy that retains the traditional PLL and VVC is proposed. In contrast to recently reported PLL-based GFM approaches, the method eliminates the need for virtual admittance control and offers higher stability robustness across a wide range of grid short-circuit ratios.
sted, utgiver, år, opplag, sider
Institute of Electrical and Electronics Engineers (IEEE) , 2026. Vol. 41, nr 1, s. 137-142
Emneord [en]
Phase locked loops, Voltage control, Grid forming, Synchronization, Inverters, Robustness, Power system stability, Regulation, Damping, Circuit stability, Grid forming (GFM), inverter-based resources (IBRs), power control and stability