This data set contains time series data of different simulated fault cases in high voltage series compensated transmission lines. The simulation is done in PSCAD using the Python automation library. The capacitor is located at one of the line terminals with CT and VT. The modelled line is 500 kV and 200 km long. The simulation is run for 1 second with 10 kHz sampling rate.
Each file contains 7 data in the following order,
Time, Voltage phase A, Voltage phase B, Voltage phase C, Current phase A, Current phase B, Current phase C.
The variables used to study different test cases are shown below,
Fault inception angle (phase A): 0 and 90 degreeSource impedance ratio: 0.20 and 0.35Capacitor level: 94 µF(50%), 78 µF(60%), 67 µF(70%)Fault resistance: 0.10, 10, 20, 30 ohmFault location: 10 km reverse, 10 km, 50 km, 100 km, 125 km, 150 km, 155 km, 160 km. 165 km, 170 km, 180 km, 190 kmFault type: No-fault, AG, BG, CG, ABG, CAG, BCG, ABCG, AB, CA, BC, ABC
All these factors lead to 6912 test cases in total. The test cases are organized in four (4) zipped folders each containing 1728 test cases. The PSCAD model file and an example python script that can be used to automate the simulations are also included herewith for anyone interested to replicate the results.
Sweden, 2021.